XC series analog expansions User Manual Page 26 of 53
MANU003R2V1
1
)
Expansion’s input/output all have options of voltage 0-5V, 0-10V, current 0-20mA, 4-20mA
modes. Via setting of special FLASH data register FD in PLC. See the following table:
Module
Channel’s ID
0CH / 3CH
4CH / 5CH
1#
expansion
FD8250
FD8251 low byte
2#
expansion
FD8258
FD8259 low byte
3#
expansion
FD8266
FD8267 low byte
4#
expansion
FD8274
FD8275 low byte
5#
expansion
FD8282
FD8283 low byte
6#
expansion
FD8290
FD8291 low byte
7#
expansion
FD8298
FD8299 low byte
Note: As shown in the preceding table, every register sets the mode of 4 channels, each register
has 16 bits, from low to high, every 4 bits sets 4 channels.
Each channel’s working mode is assigned by corresponding register’s 4 bits. Each bit’s definition
is shown in the following table:
See the following table.:
Register FD8250:
Channel 1
Channel 0
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
00
:
1/2 filter
01
:
no filter
10
:
1/3 filter
11
:
1/4 filter
0
:
voltage
input
0
:
0~10V
1
:
0~5V
00
:
1/2 filter
01
:
no filter
10
:
1/3 filter
11
:
1/4 filter
0
:
voltage
input
0
:
0~10V
1
:
0~5V
1
:
current
input
0
:
0~20mA
1
:
4~20mA
1
:
current
input
0
:
0~20
mA
1
:
4~20
mA
Channel 3
Channel 2
Bit15
Bit14
Bit13
Bit12
Bit11
Bit10
Bit9
Bit8
00
:
1/2 filter
01
:
no filter
10
:
1/3 filter
11
:
1/4 filter
0
:
voltage
input
0
:
0~10V
1
:
0~5V
00
:
1/2 filter
01
:
no filter
10
:
1/3 filter
11
:
1/4 filter
0
:
voltage
input
0
:
0~10V
1
:
0~5V
1
:
current
input
0
:
0~20mA
1
:
4~20mA
1
:
current
input
0
:
0~20
mA
1
:
4~20
mA
4-3 Working mode settings
Take 1# expansion as example:
FD8250 H O O O O
0CH
1CH
2CH
3CH
FD8251 H O O O O
4CH
5CH