XC series analog expansions User Manual Page 21 of 53
MANU003R2V1
Items
Analog input (AD)
Analog output (DA)
Voltage input
Current input
Voltage output
Current output
Analog input
range
DC 0-5V / 010V
DC 0/20mA,
4/20mA
-
Max input range
DC±18V
DC 0 / 40mA
-
Analog output
range
-
DC: 0-5V / 0-10V
(Exterior load
resistance
2KΩ~1MΩ)
DC: 0-20mA /
4-20mA
(Exterior load
resistance is
less than
500Ω)
Digital input
range
-
12 bits binary data, 0-4095
Digital output
range
14 bits binary data, 0 - 16,383
-
Bit range
1/16383(14Bit); the converted data is
stored into PLC in the format of HEX
format (14Bit)
1/4095(12Bit) the converted data
is stored into PLC with the format
of HEX. (12Bit)
PID control
value
0~4095
-
Resolution
0.8%
Conversion
speed
15ms per channel
2ms per channel
Power usage
DC24V±10%,100mA
Install format
Fixed with M3 screws or directly installed on DIN rail
External size
63mm × 102mm × 73.3mm