INSTALLATION AND DISASSEMBLY 

 

During the installation and disassembly of the module, it is recommended to cover the module with material 
which does not permeate light. 

 

It is necessary to use insulated tools during installation to minimise the risk of electrocution. 

 

The installation and disassembly must be executed in dry conditions. 

 

It  is  forbidden  to  load  the  modules  with  tools  or  objects  which  may  scratch  the  module’s  surface  
and damage the cells.  

PLACE OF INSTALLATION  

An  optimal  place  for  the  module’s  installation  allows  for  maximisation  of  power  generation,  module  security 
against damage as well as easy and safe connection of receivers which will collect the generated current. 

 

 

It is necessary to choose a place of installation that is most exposed to direct sunlight. 

 

It is necessary to avoid shaded places and places in which a part of the module is shaded for a long period of 
time.  

 

Do not install the modules near sources of heat and combustible materials. 

 

It is recommended to ensure air circulation on the module surface that is exposed to sunlight.  

METHOD OF ASSEMBLY 

The  ACTIVESOL  LIGHT  &  ULTRA  modules  may  be  assembled  using  assembly  rings,  double-sided  tape,  glue  or 
silicone. When installing flexible modules on surfaces with different thermal expansion coefficient (e.g. steel), rigid 
mounting to the surface should be avoided. The installation method should allow the module to work naturally 
without  distortions,  when  the  ambient  temperature  changes.  When  mounted,  flexible  panels  ACTIVESOL  LIGHT 
should be supported on entire surfaces. 

ELECTRICAL CONNECTION 

In the case of installation of more than one module, it is possible to use a single or parallel connection. 
Regardless of the connection, the modules of a single system should be equally exposed to sunlight. 

SERIAL CONNECTION 

The serial connection causes a voltage increase proportionate to the number of modules. In the case of the serial 
connection, it is forbidden to exceed the system’s maximum voltage (1,000 VDC).  

 

WARNING 

In a serial connection, the modules must have the same parameters and derive from a single manufacturer. 
In case of connecting more than 2 modules, the installation should be carried out by a qualified person with 
proper authorisation.  

PARALLEL CONNECTION 

The  parallel  connection  causes  a  circuit  increase  proportionate  to  the  number  of  modules.  It  is  recommended  to 
connect a maximum of 2 rows of ACTIVESOL LIGHT & ULTRA modules in a parallel circuit. In case of connecting more 
rows, it is  necessary to provide an additional security at each row (when the maximum reverse  current exceeds the 
acceptable circuit breaker load, the serial rows must be secured before they are connected to other rows). 