Configuration
3–28
975-0385-01-01
Operating without
connections
AC1 and AC2 connections can be set to “None” if operating without a connection
to a specific power source. Only stand-alone devices (in a system that includes
only the device and a System Control Panel) may be configured this way. Note
that this is not a necessary configuration step as the system will still operate with
the default settings. Using “None” where no AC source is used only serves as a
label in this case and does not modify the behavior of a unit.
Copying Settings From Another Unit
The “Copy from” command allows quick configuration of an XW Inverter/
Charger. After selecting another XW Inverter/Charger in the system to copy
settings from, common parameters are copied from the selected XW Inverter/
Charger to the XW Inverter/Charger being configured.
The following settings are copied from the selected unit:
•
Inverter Settings
•
Charger Settings
•
AC Settings
•
Grid Support Settings (except the Sell setting)
•
Gen Support Settings.
The following settings are not copied between units:
•
Inverter Mode
•
Device Number
•
Device Name
•
Auxiliary Output settings.
Figure 3-8
XW Inverter/Charger Connections Representation
L1
N
H ybrid Inverter /C harger
AC
LOAD
GRID
(AC1)
GEN
(AC2)
AC OUT
AC IN
AC IN
L 1
N
L 1
N
DC Connection:
Select House Battery 1 to 6
AC Out Connection:
Select AC Load 1 to 10
AC1 Connection:
Select Grid 1 to 10,
Gen 1 to 10
AC2 Connection:
Select Grid 1 to 10,
Gen 1 to 10