Default Settings
B–4
975-0240-01-01
Custom Battery Menu
AC Menu
Item
Default Setting
a
a.Custom battery default settings are based on the Flooded battery default settings.
The Gel and AGM default settings are provided here for reference only.
Range
Step
Size
24 V
48 V
24 V
48 V
Eqlz Support
Enabled
Enabled
Enabled, Disabled
n/a
Eqlz Voltage
32.0V
64.0V
27.0–32.0V
54.0–64.0V
0.1V
Bulk Voltage
28.8V
28.4V (Gel)
28.6V (AGM)
57.6V
56.8V (Gel)
57.2V (AGM)
20.0–32.0V
40.0–64.0V
0.1V
Absorb
Voltage
28.8V
28.4V (Gel)
28.6V (AGM)
57.6V
56.8V (Gel)
57.2V (AGM)
20.0–32.0V
40.0–64.0V
0.1V
Float Voltage
27V
27.6V (Gel)
26.8V (AGM)
54.0V
55.2V (Gel)
53.6V (AGM)
20.0–32.0V
40.0–64.0V
0.1V
Absorb Time
180min
180min
1–480min
1min
Batt Temp
Comp
27mV/C
(Flooded, Gel)
21mV/C (AGM)
108mV/C
(Flooded, Gel)
42mV/C (AGM)
0–180mV/C
1mV/C
Item
Default Setting
Range
Step Size
120 Vac
240 Vac
120 Vac
240 Vac
AC Priority
AC1
AC1, AC2
n/a
AC1 Breaker
60A
5–60A
1A
AC1 Lo Volt
106V
212V
78–115V
156–230V
1V
AC1 Hi Volt
132V
264V
125–140V
250–280V
1V
AC1 Lo Freq
55Hz
52–59Hz
1Hz
AC1 Hi Freq
65Hz
61–68Hz
1Hz
AC2 Breaker
60A
5–60A
1A
AC2 Lo Volt
80V
160V
78–115V
156–230V
1V
AC2 Hi Volt
138V
276V
125–140V
250–280V
1V
AC2 Lo Freq
55Hz
52–59Hz
1Hz
AC2 Hi Freq
65Hz
61–68Hz
1Hz