Remote Operation
SCPI Commands for Digital Interfaces
134
Operating Manual for XDC Series Power Supply
Clear
Protection
Event
To clear a protection mechanism that has tripped:
OUTP:PROT:CLE
This will clear all protection mechanisms and re-enable the output. If the condition
that caused the alarm still exists, the protection will be allowed to trip again.
View Power
Supply
Output
The following 3 commands query the voltage, current, or power being supplied at
the output terminals.
To measure the voltage output:
MEAS:VOLT?
To measure the current output:
MEAS:CURR?
To measure the power output:
MEAS:POW?
Configure
Auxiliary
Status Lines
To set up Auxiliary line A:
OUTP:AUXA:SOUR <aux-line-mnemonic>
The choices for
<aux-line-mnemonic>
include:
•
NONE
•
ON:
Output On
•
OFF:
Output Off
•
OVOL:
Over-Voltage Condition
•
UVOL:
Under-Voltage Condition
•
OCUR:
Over-Current Condition
•
UCUR:
Under-Current Condition
•
OPOW:
Over-Power Condition
•
UPOW:
Under-Power Condition
•
ACOF
: AC Power had been turned off or failed
•
OTEM:
Over-Temperature Condition
•
HTEM:
High-Temperature Condition
•
SPR:
Sense Protection Tripped
•
FOLD:
Fold Protection Tripped
•
CC:
Constant Current Mode
•
CV:
Constant Voltage Mode
•
CP:
Constant Power Mode
•
UNR:
Output Unregulated
Summary of Contents for XDC
Page 2: ......
Page 3: ...Operating Manual for XDC 6000 Watt and 12000 Watt Series Digital Programmable DC Power Supply ...
Page 22: ...List of Figures xx Operating Manual for XDC Series Power Supply ...
Page 180: ...Current Sharing 6000 Watt only Operation 178 Operating Manual for XDC Series Power Supply ...
Page 216: ...SCPI Command Reference Expressions 214 Operating Manual for XDC Series Power Supply ...
Page 228: ...GPIB Performance Specifications 226 Operating Manual for XDC Series Power Supply ...
Page 253: ......