Extended Length Installations
If the TM500A is mounted in excess of 100 feet from the inverter, an
additional wire (with a spade lugs on both ends) must be connected between
the TM500A and shunt spade lugs. This wire acts as a ground reference and
ensures the meter will read accurately.
Use the following gauge wire for the distance the TM500A is mounted
from the inverter.
Maximum Distance
Wire Gauge
250 feet
#16 AWG
400 feet
#14 AWG
630 feet
#12 AWG
1000 feet
#10 AWG
J2 TO
INVERTER
ONLY
J1 TO
SHUNT
ONLY
SPADE LUG
SPADE LUG
Interconnect for distances over
100 feet
Figure 2-6
Extended Length Ground Wire