Troubleshooting
4–4
152607
Fault Code Descriptions
Table 4-1 provides a complete description of all the fault conditions that may
occur on the PV225S.
Table 4-1
Fault Codes
Error
Code Fault
Source(s)
Fault Type
H=Hardware
S=Software
Fault Description
Possible Causes
0000
No Faults
N/A
N/A
N/A
0010
AC Frequency Low
S
This fault indicates that the Utility
grid frequency is below or fell below
the minimum allowed value of
59.3 Hz for greater than 6 cycles.
This fault is auto-clearing. Once the
Utility grid frequency has recovered
within the acceptable operating
range, the PV225S
will qualify the
value and automatically clear this
fault and resume normal operation
after 5 minute delay period.
•
Utility grid frequency
fell below the allowable
limit
0011
AC Frequency High
S
This fault indicates that the Utility
grid frequency is above or rose above
the maximum allowed value of
60.5Hz for greater than 6 cycles. This
fault is auto-clearing. Once the Utility
grid frequency has recovered within
the acceptable operating range, the
PV225S
will qualify the value and
automatically clear this fault and
resume normal operation after
5 minute delay period.
•
Utility grid frequency
rose above the
allowable limit
0012
AC Voltage Low
S
This fault indicates that the utility
grid voltage is below or fell below the
minimum allowed value of 88% of
nominal Vac for greater than
2 seconds, or 50% of nominal VAC
for greater than 6 cycles. This fault is
auto-clearing. Once the Utility grid
voltage has recovered within the
acceptable operating range, the
PV225S
will qualify the value and
automatically clear this fault and
resume normal operation after
5 minute delay period.
•
Utility grid voltage fell
below the allowable
limit
•
Fuses F1, F2, F3, F7, F8
or F9 blown
•
P1001 on CCU2 is
loose or disconnected
Summary of Contents for PV225S-480-P
Page 1: ...PV225S 225 kW Grid Tied Photovoltaic Inverter PV225S 480 P Operation and Maintenance Manual...
Page 2: ......
Page 3: ...PV225S 225 kW Grid Tied Photovoltaic Inverter Operation and Maintenance Manual...
Page 8: ...vi...
Page 14: ...xii...
Page 22: ...xx...
Page 78: ...2 38...
Page 79: ...Computer Communications with the PV225S 152607 2 39...
Page 80: ...Operation 2 40 152607...
Page 88: ...3 8...
Page 102: ...4 14...
Page 110: ...5 8...
Page 115: ...Appendix A Schematics 152607 A 5 Figure A 1 Electrical Diagram sample...
Page 122: ...WA 4...
Page 125: ......