Clearing Faults Manually
152379 Rev C
4–3
Clearing Faults Manually
Faults associated with a grid disturbance clear automatically. These faults include:
•
0010 (AC Frequency Low),
•
0011 (AC Frequency High),
•
0012 AC Voltage Low), and
•
0013 (AC Voltage High) only.
Once the AC voltage and frequency return to within the acceptable range, the
PV100S will clear the fault and automatically restart after a 5-minute delay. All
other faults associated with the PV100S must be circumvented and cleared
manually using the UFCU.The following procedure describes how to manually
clear a fault message from the LCD.
To clear the fault:
1. Determine the source of the fault using Table 4-1, “Fault Codes” on page 4–4.
Correct the fault condition.
2. Ensure the fault code and “
Clear Fault?
” message is displayed in the LCD.
a) If the “
Clear Fault?
” message is not shown on the second line of the
LCD, scroll through the read parameter menu with the
/\
or
\/
keys until
the message appears.
3. To clear the fault, press <
E
NTER
>. The PV100S will transition to Sleeping
mode.
Figure 4-1
LCD showing Fault Code
Important:
If the fault does not clear, the fault condition has not been corrected.
LCD Display showing
Fault Code
UFCU Keypad
0071
PV SWITCH OPEN
F1 to Clear Fault?
Goal: PWR TRACKING
Summary of Contents for PV100S-208
Page 2: ......
Page 3: ...s PV100S 100 kW Grid Tied Photovoltaic Inverter Operation and Maintenance Manual...
Page 8: ...vi...
Page 14: ...xii...
Page 22: ...xx...
Page 78: ...2 38...
Page 86: ...3 8...
Page 104: ...5 8...
Page 109: ...Appendix A Schematics 152379 Rev C A 5 Figure A 1 Electrical Diagram sample...
Page 116: ...Schematics Appendix A A 12 152379 Rev C This page intentionally left blank...
Page 120: ...Warranty and Return WA 4 152379 Rev C...
Page 123: ......