Adjusting Feature Settings in Configuration Mode
975-1175-01-01
45
Setting Name
Setting
Number
Default
Value
Range of Values
Description
Output Frequency
07
60
60
50
After changing the output frequency setting, turn the unit off
and then on again, in order for the change to take effect.
Output Voltage
08
120
120
110
108
Inverter Output
Power Limit
09
1
.
8
0
.
1
to
1
.
8
The wattage setting value can be adjusted by 100-W
increments. Use with Inverter Output Power Limit Timer
especially when pairing with a lithium ion battery. 0.1 is
equivalent to 100 W.
Inverter Output
Power Limit Timer
10
300
1
to
300
When the range is from 1 to 20, the timer setting value can be
adjusted by 1-s increments. When the range is from 20 to 300,
the timer setting value can be adjusted by 10-s increments.
Use with Inverter Output Power especially when pairing with a
lithium ion battery. The timer is automatically disabled if the
maximum Inverter Output Power limit is selected.
Transfer Mode
11
APL
APL
(appliance)
,
UPS
(UPS)
Selecting
APL
- appliance sets the transfer time from line to
battery to 20 ms. Selecting
UPS
(uninterruptible power supply)
sets the transfer time from line to battery to 10 ms.
NOTE
: Do not connect motor loads when in
UPS
transfer
mode. See “Troubleshooting”.