Xtreme Power Conversion Corporation
TX90 6kVA & 10kVA User’s Manual
Page 14
Uninterruptible Power Supply
Output Configuration
All of the output options shown below apply to 208V input systems and 240V input systems.
Option 1: 120V/240VAC - THIS IS THE DEFAULT OPTION FOR ALL UNITS
: Each branch max loading 50%. Please
note the jumpers between G2-L22 and L22-N21 for this option.
Option 2:
120V full capacity output. Please note the jumpers between G2-N22, N22-N21, and L22-L21 for this
option. See below.
For any other output configurations needed, please contact Xtreme Power Tech Support.
Please refer to the specifications of input current, output current and recommended conductors listed below.
a.
AC input and output (minimum 75°C copper wire)
Model
Maximum Input
Current
Input Breaker Size
Input & Output
Conductor Section
Terminal Torque
Force
6KVA
33 A
40 A
AWG #8
17.7/11 lb-in
10KVA
54.3 A
60 A
AWG #6
23 lb-in
b.
Battery input
Model
Maximum Current
Conductor Section
6KVA
25 A
AWG #10
10KVA
41 A
AWG #10