WIRING THE FIXTURE

 

CAUTION 

Wiring should only be performed by a professional electrician. 

General

 

Connection of the individual ballast input leads and incandescent socket leads must be made at the time of the installation. 
Series ballast circuitry is used in the X-Rite Overhead Luminaires. In order to accommodate possible installation 
requirements, wire entry for input power is possible from either end of the fixture. 

Note:   

All leads are arranged so that the knockouts at one end of the fixture are desirable for wire entry. If you use the 

other end of the fixture, note that all input wiring within 3 inches of the ballast and socket will tolerate 90° C 

 

 

Number of 

Lamps

 

Ballasts 

and AC 

Power 
Inputs

 

Ballast

 

Control

 

Assignments

 

Ballast

 

Wiring Assignments

 

(Note: Use Wire Nuts on All Connections)

 

 
 

PLD-440

 

4 Fluorescent

 

2 Ballasts 1 

Input

 

Ballast 1: Lamps 1 and 2 

Ballast 2: Lamps 3 and 4

 

Black 

ballast leads go to 

black 

AC power input. 

White 

ballast leads go to 

white 

AC power input. Ground from 

AC power input goes to fixture ground.

 

 
PLD-840

 

(Single

 

Source)

 

8 Fluorescent

 

4 Ballasts 1 

Input

 

Ballast 1: Lamps 1 and 3 

Ballast 2: Lamps 2 and 4 

Ballast 3: Lamps 5 and 7 

Ballast 4: Lamps 6 and 8

 

Black 

ballast leads go to 

black 

AC power input. 

White 

ballast leads go to 

white 

AC power input. Ground from 

AC power input goes to fixture ground.

 

 
 
 
PLD-840

 

(Dual

 

Source)

 

2 Sets of 4 

Fluorescent

 

4 Ballasts 2 

Inputs

 

Ballast 1: Lamps 1 and 3 

Ballast 2: Lamps 2 and 4 

Ballast 3: Lamps 5 and 7 

Ballast 4: Lamps 6 and 8

 

Black 

leads for ballasts 1 and 3 go to 

black 

AC power input on 

first AC source.

 

White 

leads for ballasts 1 and 3 go to 

white 

AC power input on 

first AC source.

 

Black 

leads for ballasts 2 and 4 go to 

black 

AC power input on 

second AC source.

 

White 

leads for ballasts 2 and 4 go to 

white 

AC power input on 

second AC source.

 

Ground from AC power input goes to fixture ground.

 

 
 

TC-440B

 

4 Fluorescent 4 

Incandescent

 

2 Ballasts 1 

Input

 

Ballast 1: Lamps 1 and 2 

Ballast 2: Lamps 3 and 4

 

Black 

ballast and incandescent leads go to 

black 

AC power 

input.

 

White 

ballast and incandescent leads go to 

white 

AC power 

input.

 

Ground from AC power input goes to fixture ground.

 

 
 
 
 
 
 
 

SD-840B

 

4 Daylight 

Fluorescent

 

4 Cool White 
Fluorescent

 

8 Incandescent

 

4 Ballasts 3 

Inputs

 

Ballast 1: Lamps 1 and 3 

Ballast 2: Lamps 2 and 4 

Ballast 3: Lamps 5 and 7 

Ballast 4: Lamps 6 and 8

 

Black 

leads for ballasts 1 and 3 go to 

black 

AC power input on 

first AC source.

 

White 

leads for ballasts 1 and 3 go to 

white 

AC power input on 

first AC source.

 

Black 

leads for ballasts 2 and 4 go to 

black 

AC power input on 

second AC source.

 

White 

leads for ballasts 2 and 4 go to 

white 

AC power input on 

second AC source.

 

Black 

incandescent socket leads go to 

black 

AC power input on 

third AC source.

 

White 

incandescent socket leads go to 

white 

AC power input on 

third AC source.

 

Ground from AC power input goes to fixture ground.

 

Summary of Contents for Examolite TC-440B

Page 1: ...operation KEEP INSTRUCTIONS Retain these instructions for future reference Once you have read these instructions keep them available for other operators to read OBEY ALL WARNINGS Please comply with a...

Page 2: ...ires are designed for 100VAC 50Hz 117VAC 60Hz 220VAC 50Hz 240VAC 50Hz or 277VAC 60Hz operation In all cases proper input power is marked on the box and fixture label CAUTION Do not operate fixture on...

Page 3: ...cific electrical needs 6 If you are mounting the fixture into a standard grid ceiling follow the accepted mounting practices for your building code If the fixture is to be chain hung over a work surfa...

Page 4: ...r Fixture Net Weights Proof lite PLD 4 lamp 57 5 lbs 25 87 kg Prooflite PLD 8 lamp 68 0 lbs 30 6 kg Examolite TC 440B 78 0 lbs 35 1 kg Examolite SD 840B 90 0 lbs 40 5 kg On the rear of the fixture hou...

Page 5: ...PLD 840 Dual Source 2 Sets of 4 Fluorescent 4 Ballasts 2 Inputs Ballast 1 Lamps 1 and 3 Ballast 2 Lamps 2 and 4 Ballast 3 Lamps 5 and 7 Ballast 4 Lamps 6 and 8 Black leads for ballasts 1 and 3 go to...

Page 6: ...is parallel to the longest side of the luminaire Replacement of Lamps Replace lamps at approximately 75 percent of their rated life expectancy to retain spectral characteristics Replace burned out lam...

Page 7: ...incandescent lamps Dimensions Length 48 in 121 19 cm Width 23 75 in 60 3 cm Height 8 in 20 3 cm Weight 78 0 lbs 35 4 kg 90 0 lbs 40 8 kg Power Consumption 368 watts 552 watts Electrical Requirements 1...

Page 8: ...8 incandescent lamps are required for each overhead fixture Lamps are sold in packages of sixteen 16 or as part of a specific lamp kit Examolite SD 840B 5000K Replacement Lamp Kit A LK ESD8450 This k...

Page 9: ...not be liable for errors contained herein or for incidental or consequential damages in connection with the performance or use of this material This manual as well as any revisions are the copyright o...

Page 10: ...7 or 1 616 803 2705 Corporate Headquarters Europe Althardstrasse 70 8105 Regensdorf Switzerland Phone 41 44 842 24 00 Fax 41 44 842 22 22 Corporate Headquarters Asia Room 808 810 Kornhill Metro Tower...

Reviews: