26
6.2 Mounting
Heed the following points when selecting the installation site for the
LATENTO
XW:
Frost-protected room.
Level, clean swept floor.
Do not subject the
LATENTO
to direct solar radiation
(the UV can destroy the plastic).
Heed the load-bearing capacity of the foundation, the filled
LATENTO
500
weighs approx. 650 kg.
Keeping heat-losses as little as can be, place the
LATENTO
in the vicinity of the
reheating heat generator.
If possible, mount system in a heated room to minimize heat-losses
(ENEV – Energy Saving Decree).
Note
For operation with electrical heating element (878 700 039):
The screwing of the electrical heating element into the
LATENTO
storage tank should take place before its filling and piping.
In areas with low room height it can be necessary to tilt the
LATENTO
storage tank in order to insert the electrical heating
element.
6.3 Pipework
Caution
Heed the regulations of the local water distribution company
and relevant DIN standards when connecting. The connections
must be made pressure-tight. The component-tested safety instal-
lations have to be installed according to DIN 4753, Part 1,
para. 6.3-7 (safety valve, reflux valve, pressure reducing valve,
drainage, control and safety device).
A thermal mixing valve (Item no. 878 700 021) must be installed to the hot water
outlet of the domestic water heat exchanger so as to prevent scalds. The hot water
heat exchanger should be 60 °C according to DIN EN 806-2 (June 2005).
Summary of Contents for IVT LATENTO 500
Page 17: ...D 17 Produktdatenblatt ...
Page 19: ...E Illustrations similar LATENTO 500 Unpressurized hot water storage tank Mounting instruction ...
Page 36: ......
Page 37: ...F Fig similaire LATENTO 500 Accumulateur d eau chaude Notice de montage ...
Page 54: ......
Page 55: ...ES Fig similar LATENTO 500 Acumulador de agua caliente Instrucciones de montaje ...
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......