WURM FRIGOLINK ANI-1F1 Manual Download Page 12

ANI-1F1

12

ANI-1F1_V2.1.4_PI_2018-06_EN.fm

Subject to technical changes

FRIGOLINK

Dismantling

1. Insert a flat-tip screwdriver in the openings in the fastening catches.
2. Pull the two fastening catches away from the housing until they are heard to click.
3. Swivel the bottom of the module gently away from the top-hat rail and towards yourself.
4. Lift the module upwards away from the top-hat rail.

1.5 Technical data

For details of input assignments, see: Paragraph 1.3.1 "Input circuit diagram" on page 5

For details of output assignments, see: Paragraph 1.3.2 "Output circuit diagram" on page 8

For details of sensor assignments, see: Paragraph  "Analogue inputs S 1 - S 16" on page 7

Power supply

230V~, +10% / -15%, 50Hz, max. 13VA

Display

Optional control element with graphic display
1 x LED (green/red), operating voltage: green, fault: red
4 x LED (green), CAN bus data traffic (CAN Tx, CAN Rx)

Sensors

16 x DGF/TRK

Communication C-BUS

3-wire CAN bus interface, shielded, galvanically isolated, screw 
terminals 2.5mm

2

 and RJ45 socket

Communication F-BUS

3-wire CAN bus interface, shielded, galvanically isolated, screw 
terminals 2.5mm

2

 and RJ45 socket

Analogue inputs

5 x 4...20mA, 23V=power supply
2 x 0...10V=

Digital inputs

20 x potential-free for 230V~ (neutral conductor N per input)

Analogue outputs

5 x 0...10V=, non-isolated, max. load 10mA

Digital outputs

2 x mechanical relays 4(2)A@230V~ (changeover contact)
12 x mechanical relays 4(2)A@230V~ (normally open contact)
4x semiconductor relays 4...60VA@230V~

Dimensions

(WxHxD) 270 x 80 x 165

Housing

Plastic

Fastening

Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715)

Ambient temperature

Operation: -20...+55°C, storage: -25...+70°C

Weight

About 1125g

CE conformity

EU conformity as defined in
-

2014/30/EU (EMC Directive)

-

2014/35/EU (Low Voltage Directive)

RoHS II

Valid from

Version 2.1.4

Summary of Contents for FRIGOLINK ANI-1F1

Page 1: ...gas temperature Oscillation protection function Blocking time after compressor fault Two step load shedding and fast return flow Operating hours counter for each compressor Low temperature compressor...

Page 2: ...rcuit diagram 5 Digital inputs DI 1 DI 20 5 Analogue inputs Uin 1 2 6 Analogue inputs Iin 1 Iin 5 6 Analogue inputs S 1 S 16 7 1 3 2 Output circuit diagram 8 Digital outputs relays K 1 K 14 8 Digital...

Page 3: ...intended purpose Warnung WARNING DANGER TO LIFE FROM ELECTRIC SHOCK AND OR FIRE Switch off the power to the entire plant when installing wiring or removing Otherwise a mains voltage and or external v...

Page 4: ...58 160 151 153 155 157 159 Relay K 3 14 Relay K1 K2 Solid State Relay V 1 4 0 10V Analog Output Uout 1 5 0 10V Analog Input Uin 1 2 4 20mA Analog Input Iin 1 5 Digital Inputs DI 1 20 230V 50Hz 140 130...

Page 5: ...1 5 0 10V Analog Input Uin 1 2 4 20mA Analog Input Iin 1 5 Digital Inputs DI 1 20 230V 50Hz 140 130 N 20 11 neutral terminal DI 10 1 230V 120 110 131 121 111 101 DI 20 11 230V N 10 1 neutral terminal...

Page 6: ...ult PSL LP com pound 136 N 127 DI 17 230V Fault HP compound 137 N 128 DI 18 230V Fault in GC fan 1 138 N 129 DI 19 230V UPS fault 139 N 130 DI 20 230V Fault RC protection 140 N Terminal Analogue input...

Page 7: ...S 3 DGF Pressure gas temper ature LT compressor desuperheating 167 168 S 4 TRK External temperature 169 170 S 5 DGF Temperature gas cooler outlet T GK 1 171 172 S 6 DGF Temperature gas cooler outlet T...

Page 8: ...Output Uout 1 5 0 10V Analog Input Uin 1 2 4 20mA Analog Input Iin 1 5 Digital Inputs DI 1 20 230V 50Hz 140 130 N 20 11 neutral terminal DI 10 1 230V 120 110 131 121 111 101 DI 20 11 230V N 10 1 neut...

Page 9: ...output SSR Contact arrange ment Assignment 231 Semiconductor V 1 4 60VA 230V NO MT HG bypass valve suction gas monitor ing 232 COM 233 Semiconductor V 2 4 60VA 230V NO Post injection MT 234 COM 235 Se...

Page 10: ...each 4 2 A 230V 211 201 210 K 1 4 each 4 2 A 230V 220 K 10 14 each 4 2 A 230V 221 230 S16 194 S 15 11 Sensor 190 191 181 S 10 6 Sensor 180 171 170 S 5 1 Sensor 161 Iin 1 5 4 20mA 160 151 Uin 2 1 0 10...

Page 11: ...tage is switched off Top hat rail installation 1 There are 2 fastening catches located on the back of the module A Press both catches a downward until they engage with a click 2 There are 4 retaining...

Page 12: ...ting voltage green fault red 4 x LED green CAN bus data traffic CAN Tx CAN Rx Sensors 16 x DGF TRK Communication C BUS 3 wire CAN bus interface shielded galvanically isolated screw terminals 2 5mm2 an...

Reviews: