background image

Western Reserve Controls 

   

W5-JEM1 Wiring & Installation 

Revision 1.0 

 

 

3

 

 

PUB005-20190314-A01

 

 

Hardware Installation and Set-Up 

1.2 

Installation 

Follow the steps below: 

1. 

In most cases it is recommended to set the device’s IP address prior to installation. See W5-JEM1 
User Manual for complete instructions.  

a.  Note: factory default IP address is 192.168.1.10 for all units 

2.  Mount unit onto DIN rail 

3.  Wire  up  power  (24VDC  typical),  common,  and  chassis  ground  to  the  power  connector.  See 

“Connector Pinouts” for a diagram. 

a.  If  there  is  no  chassis  ground  connection,  or  the  power  supply  is  connected  to  chassis 

ground, jumper the chassis ground connection to the common connection 

4.  Connect the device to the controlling PLC with an Ethernet cable 

a.  The device may be connected directly or through an ethernet switch 

5.  Connect the W5-JEM1 to the serial device using a compatible serial cable 

a.  This  device  requires  serial  cables  with  a  special  pinout.  See  section  1.8 

“Serial  Wiring 

Diagrams

 and section 1.7 “Connector Pinouts” for further information. 

6.  Apply power, device is ready for use with PLC. 

7.  Also see W5-JEM1 User Manual for an explanation of how to use the W5-JEM1 with a PLC 

1.3 

Power Supply 

The device is intended to be used with standard 24V DC industrial power supplies. However, any voltage 
between 5V and 28V may be supplied to the device assuming sufficient current is provided.  

1.4 

Network Connection 

The  device  must  be  connected  to  the  controlling  PLC  either  directly  with  a  cable  or  through  your  local 
network Ethernet switch.  

 

 

 

 

 

 

Figure 1. Several possible ethernet network configurations 

Summary of Contents for W5-JEM1

Page 1: ...ion Instructions W5 JEM1 EtherNet IP to RS 232 485 Serial Device Gateway Cost optimized multi protocol ASCII gateway perfect for RS 232 485 Serial Device Integration Document PUB005 20190314 A01 Rev 1...

Page 2: ...eed 10 100 MBits IP Address selection Static IP configured via web browser Factory Default 192 168 1 10 Power Supply 5 0 28 0 Vdc 1A user replaceable fuse spare fuse included Maximum Power 2 4W 100mA...

Page 3: ...controlling PLC with an Ethernet cable a The device may be connected directly or through an ethernet switch 5 Connect the W5 JEM1 to the serial device using a compatible serial cable a This device req...

Page 4: ...le Status LED labeled MS LED State Module Status Meaning Off No Power Device is not powered Green Device Operational W5 JEM1 is operating normally Flashing Red Minor Fault Recoverable fault Solid Red...

Page 5: ...a piece of standard DIN rail This drawing does not include the overall height or length added by the Power Serial or Ethernet cables or their respective connectors Side View Top View 1 7 Connector Pi...

Page 6: ...nnect Do Not Connect 3 Transmit Data Do Not Connect Do Not Connect 4 Do Not Connect Receive Data Do Not Connect 5 Common Common Common 6 Do Not Connect Receive Data Do Not Connect 7 Request To Send Re...

Page 7: ...ng Installation Revision 1 0 7 PUB005 20190314 A01 Figure 6 RS 422 Wiring Diagram Figure 7 RS 485 Wiring Diagram 1 9 Models and Part Numbers WRC Order Number Description W5 JEM1 DH2 DIN Mount Serial t...

Reviews: