11
General information
Greenstar Heatslave II External
ErP
– 6 720 813 722 (2014/09)
5
General information
5.1
Important information
Fuel
This appliance is designed to use 28 second kerosene, no other
fuel must be used.
Boiler location
To prevent “wetting” it is recommended that the flue terminal
faces away from walls.
Never allow the flue terminal or air inlet to become
obstructed by plants or any other objects.
This boiler is only suitable for installing externally at a suitable
location onto a fixed, permanent, rigid surface capable of
supporting the boiler weight. Wood and tarmac hardstandings
are not recommended.
The boiler must be installed on a flat level surface to ensure that
condensate does not enter the primary heat exchanger.
The cabinet is not load bearing, and only provides weather
protection for the boiler inside.
There must be sufficient hard standing and access around the
boiler for servicing.
Installation & servicing clearances
Fig. 9
WARNING:
External equipment operating at
230 Volts must not be serviced or repaired
during adverse weather conditions.
Do not use pressure washers or steam
cleaners on this appliance or cabinet.
WARNING:
This boiler must not be installed
where there is a potential for excessive ground
water coverage.
FRO
N
T
FRONT
FRONT
BASE
Plan
view
Plan
view
2500mm
2500mm
2500mm
600mm
600mm
600mm
600mm
50mm
10mm
85mm
45mm
6 720 805 212-02.1TL
The same applies
for right hand flue
installation where
right and left
clearances are
mirrored.