Rectifying faults
29
6.
Is the ground connection correct?
yes:
↓
no:
B
Rewire correctly as specified in the installation
instructions.
B
Press
, does appliance restart???
EA?
7.
Two phase net:
Is there a resistor fitted between Pe
and N?
yes:
↓
no:
B
Power OFF the appliance.
B
Disconnect the boiler electrical connection.
B
Insert resistance (Order no. 8 900 431 516)
between the ground and the N connection.
B
Reconnect the boiler electrical connection.
B
Turn ON the appliance.
B
Press
, does appliance restart???
EA?
↓
8.
Is condensation trap in condensing
boiler blocked?
yes:
B
Unscrew condensation trap and clean.
B
Press
, does appliance restart???
EA?
no:
↓
9.
Check the gas valve?
B
Power OFF the appliance.
B
Unplug the connectors from the
gas valve.
B
Measure the gas valve coils
I
and
II
electrical resistance.
R =164
±
40
Ω
?
yes:
B
Reconnect the gas valve.
B
Turn ON the appliance.
B
Press
, does appliance restart???
EA?
↓
no:
B
Change the gas valve.
B
Reconnect the gas valve.
B
Turn ON the appliance.
B
Press
, does appliance restart???
EA?
↓
10.
Is flue blocked?
B
Check CO
2
level in combustion
air.
> 0,2 % CO
2
?
yes:
B
Check the flue.
B
Press
, does appliance restart???
EA?
↓
no:
↓
EA
and
flashing.
During operation: flame not detected
Check
Action
Summary of Contents for GREENSTAR HE combi Series