DISPLAY INFORMATION
6 720 648 726 (2011/07)
73
e
[0/y/\|
e
[2/0/4|
Operating phase:
The flow temperature sensor has detected
that the current flow temperature is higher
than the flow temperature setting on the
BC10, or that it is higher than the flow
temperature. Calculated according to
heating requirements, or that it is higher
than the flow temperature calculated for the
DHW mode.
Off
The room
temperature is not
possibly reached.
e
[0/y/\|
e
[2/7/6|
e
Fault:
The flow temperature sensor has measured
a current flow temperature higher than
95 °C.
No
4)
5)
Off
The room
temperature is not
possibly reached.
e
[0/y/\|
e
[2/7/7|
e
Fault:
The safety temperature sensor has
measured a current safety temperature
higher than 95 °C.
No
Off
The room
temperature is not
possibly reached.
e
[0/y/\|
e
[2/8/5|
e
Fault:
The return temperature sensor has
measured a current return temperature
higher than 95 °C.
No
Off
The room
temperature is not
possibly reached.
e
[1/l/\|
e
[2/1/1|
e
Fault:
There is no connection between contacts 78
and 50 of the UBA 3 installation base.
No
Off
No heating operation
and no DHW.
e
[2/e/\|
e
[2/0/7|
e
Fault:
The system pressure is too low (less than
0.2 bar).
No
Off
No heating operation
and no DHW.
e
[2/f/\|
e
[2/6/0|
e
Fault:
The flow temperature sensor has not, after
burner start-up, detected any temperature
increase in the heating system water.
No
Off
e
[2/f/\|
e
[2/7/1|
e
Fault:
The heating water temperature difference,
measured between the flow temperature
sensor and the safety temperature sensor, is
too high.
Display codes
Display code
LED on
UBA 3
Other effects
z
Main
display
code
z
Sub
display
code
z
Key to display code
Reset
requi-
red?
Table 24 Display codes