INSTALLATION
6 720 648 726 (2011/07)
34
INSTALLING AND CONNECTING OTHER
CONTROLLERS OUTSIDE THE BOILER
B
Install the controller as described in the relevant
installation instructions.
B
Connect a RC25 or RC35 room controller or a 4121,
4122 or 4323 cascade controller to the orange RC
terminal using a 2-core cable of 0.75 mm².
Fig. 46 Terminal strip – Room controller RC and EMS bus
(connection colour orange)
CONNECTING THE OUTDOOR TEMPERATURE
SENSOR
If outdoor temperature-dependant control operation is
used, an outdoor temperature sensor must be
connected.
B
Connect the outdoor temperature sensor to the blue
FA terminal, using a 2-core cable of 0.75 mm².
Fig. 47 Terminal strip - Outdoor-temperature sensor
(connection colour blue)
CONNECTING THE POTENTIAL-FREE HEAT DEMAND
B
Connect the potential-free heat demand contact to
the green WA terminal (
Æ
fig. 48). The maximum
allowed resistance of this circuit is 100 ohms.
Use a 2-core cable of 0.75 mm².
Fig. 48 Terminal strip - potential-free heat demand
(connection colour green)
Fig. 49 Terminal strip - WA potential-free heat demand
If you install the room controller (e.g. RC35)
in the boiler, only outdoor temperature-
controlled operation is possible. See the
room controller user manual for further
information.
This connection is reverse-proof. This
means that it does not matter in which order
the wires are connected.
This connection is non polarity sensitive.
This means that it does not matter which
order the wires are connected.
RC
6 720 648 726-046.1TD
FA
6 720 648 726-047.1TD
NOTE:
B
It is not possible to connect a thermostat
simultaneously to the RC connection and
to the terminal for the potential-free heat
demand (WA) (
Æ
fig. 49).
B
It is possible to operate the boiler with an
On/Off contact for potential-free heat
demand, but the room temperature-
based modulating function of the boiler
cannot then be used anymore. This has a
negative effect on comfort and energy
consumption. If an On/Off contact for
potential-free heat demand is installed,
the boiler will only modulate up to the
preset CH flow temperature.
B
This connection is reverse-proof. This
means that it does not matter which
order the wires are connected.
WA
6 720 648 726-048.1TD
WA
6 720 648 726-048.1TD