Manual 26185
TecJet 110 Fuel Metering System
Woodward
19
Byte 5
Bit 0: BATTERY_VOLT_LOW_ERR
Bit 1: FGT_LOW_LIMIT_ERR
Bit 2: DELTA_P_LOW_LIMIT_ERR
Bit 3: FGP_LOW_LIMIT_ERR
Bit 4: BATTERY_VOLT_HIGH_ERR
Bit 5: FGT_HIGH_LIMIT_ERR
Bit 6: DELTA_P_HIGH_LIMIT_ERR
Bit 7: FGP_HIGH_LIMIT_ERR
Byte 6
Bit 0: RESERVED
Bit 1: WATCHDOG_RESET
Bit 2: RESERVED
Bit 3: RESERVED
Bit 4: CAN_FLOW_DEMAND_FAILED
Bit 5: RESERVED
Bit 6: TECJECT_SHUTDOWN
Bit 7: TECJET_INTERNAL_FAULT
Byte 7
Bit 0: RESERVED
Bit 1: KEYSWITCH_STATE
Bit 2: RESERVED
Bit 3: RESERVED
Bit 4: RESERVED
Bit 5: RESERVED
Bit 6: RESERVED
Bit 7: RESERVED
Byte 8
Bit 0: RESERVED
Bit 1: RESERVED
Bit 2: RESERVED
Bit 3: RESERVED
Bit 4: RESERVED
Bit 5: RESERVED
Bit 6: RESERVED
Bit 7: RESERVED
Address Claimed
The Address Claimed message will be sent out shortly after power has been
applied to the TecJet 50 Plus if the TecJet is configured for the
EGS-02 Flow Demand mode.
The Address Claimed message will be sent out in response to a Request for
Address Claimed if the preferred address was successfully claimed or if the
TecJet has not won or lost address claiming.
The Request for Address Claimed can be sent to a specific Address or to the
Global Destination Address, 255. The TecJet 50 Plus will respond to a specific
query, or one to the Global Destination Address, 255
The Source Address for this transmit message will be 18 for TecJet 1, 125 for
TecJet 2, 126 for TecJet 3, 127 for TecJet 4. Addresses are not re-
programmable.
The Address Claimed Message will also be sent out if the TecJet 50 Plus
receives an Address Claimed message from the same Address as the receiving
node and a lower priority (higher value) NAME. The entire 8-byte value of the
NAME is used for arbitration with the Arbitrary Address Capable Field as the
Most Significant Bit.