Woodward TecJet 110 Installation And Operation Manual Download Page 25

Manual 26185 

TecJet 110 Fuel Metering System 

 

 

 

Woodward 

19 

Byte 5 

Bit 0: BATTERY_VOLT_LOW_ERR 
Bit 1: FGT_LOW_LIMIT_ERR 
Bit 2: DELTA_P_LOW_LIMIT_ERR 
Bit 3: FGP_LOW_LIMIT_ERR 
Bit 4: BATTERY_VOLT_HIGH_ERR 
Bit 5: FGT_HIGH_LIMIT_ERR 
Bit 6: DELTA_P_HIGH_LIMIT_ERR 
Bit 7: FGP_HIGH_LIMIT_ERR 

Byte 6 

Bit 0: RESERVED 
Bit 1: WATCHDOG_RESET 
Bit 2: RESERVED 
Bit 3: RESERVED 
Bit 4: CAN_FLOW_DEMAND_FAILED 
Bit 5: RESERVED 
Bit 6: TECJECT_SHUTDOWN 
Bit 7: TECJET_INTERNAL_FAULT 

Byte 7 

Bit 0: RESERVED 
Bit 1: KEYSWITCH_STATE 
Bit 2: RESERVED 
Bit 3: RESERVED 
Bit 4: RESERVED 
Bit 5: RESERVED 
Bit 6: RESERVED 
Bit 7: RESERVED 

Byte 8 

Bit 0: RESERVED 
Bit 1: RESERVED 
Bit 2: RESERVED 
Bit 3: RESERVED 
Bit 4: RESERVED 
Bit 5: RESERVED 
Bit 6: RESERVED 
Bit 7: RESERVED 

Address Claimed 

The Address Claimed message will be sent out shortly after power has been 
applied to the TecJet 50 Plus if the TecJet is configured for the  
EGS-02 Flow Demand mode. 
The Address Claimed message will be sent out in response to a Request for 
Address Claimed if the preferred address was successfully claimed or if the 
TecJet has not won or lost address claiming. 
The Request for Address Claimed can be sent to a specific Address or to the 
Global Destination Address, 255. The TecJet 50 Plus will respond to a specific 
query, or one to the Global Destination Address, 255 
The Source Address for this transmit message will be 18 for TecJet 1, 125 for 
TecJet 2, 126 for TecJet 3, 127 for TecJet 4. Addresses are not re-
programmable. 
The Address Claimed Message will also be sent out if the TecJet 50 Plus 
receives an Address Claimed message from the same Address as the receiving 
node and a lower priority (higher value) NAME. The entire 8-byte value of the 
NAME is used for arbitration with the Arbitrary Address Capable Field as the 
Most Significant Bit. 

 

 

Summary of Contents for TecJet 110

Page 1: ...Installation and Operation Manual TecJet 110 Gas Regulation and Metering Valve Actuator System Manual 26185 Revision F...

Page 2: ...heck the Woodward website www woodward com pubs current pdf The revision level is shown at the bottom of the front cover after the publication number The latest version of most publications is availab...

Page 3: ...ination 8 CAN In 8 CAN Out 8 CAN Shield 9 4 20mA Analog Input 9 Status Output 9 RS 232 Serial Communication Service Port 9 CHAPTER 3 DESCRIPTION OF OPERATION 10 Configuration 10 Power on Procedure 10...

Page 4: ...neering Services 41 How to Contact Woodward 41 Technical Assistance 42 DECLARATIONS 44 Illustrations and Tables Figure 2 1 TecJet 110 Outline Drawing 3 Figure 2 2 TecJet 110 Valve Wiring Diagram 5 Fig...

Page 5: ...trical connections while circuit is live unless the area is known to be non hazardous Substitution of components may impair suitability for Class I Division 2 or Zone 2 applications RISQUE D EXPLOSION...

Page 6: ...materials such as plastic or Styrofoam cups cup holders cigarette packages cellophane wrappers vinyl books or folders plastic bottles and plastic ash trays away from the control the modules and the w...

Page 7: ...Throughout the remainder of the manual the TecJet 110 valve and actuator system will be referred to simply as the TecJet 110 Connections to the TecJet 110 The TecJet 110 valve has the following connec...

Page 8: ...ition pointer Mounting TecJet 110 orientation and mounting must be designed to reduce the possibility of fuel contamination Orientation of the valve should be with the actuator 15 relative to horizont...

Page 9: ...Manual 26185 TecJet 110 Fuel Metering System Woodward 3 Figure 2 1 TecJet 110 Outline Drawing...

Page 10: ...r wire type and wiring practices are critical to operation Do not connect any cable grounds to instrument ground control ground or any non earth ground system Make all required electrical connections...

Page 11: ...N Hi In CAN Lo In CAN Shield CAN Hi Out CAN Lo Out PWM In Keyswitch Power In Power In TecJet 110 Jumper for CAN Termination Resistor Z W F L K B A Q P U T X S R PWM In 4 20mA Analog In 4 20mA Analog I...

Page 12: ...Recommended maximum wire length from power source to TecJet 110 valve based on an 18 V Power Supply 16 AWG 1 3 mm 8 m 26 ft Rated transient torque may not be achievable with an 18 V power supply Liste...

Page 13: ...ID Inputs H CAN ID 1 G CAN ID 2 J Discrete RS232 Common The CAN ID inputs are used to select which CAN identifiers will be used on the CANbus With no programming tools the customer can select from the...

Page 14: ...devices on the CANbus that must not lose communication when the TecJet 110 valve is disconnected CAN In R CAN high in S CAN low in V CAN GND Pins R S and V are the CAN communication wires Make sure th...

Page 15: ...erature Drift 300ppm C Status Output E Status Output J Discrete RS232 Common The status output indicates whether the TecJet 110 valve is operating correctly It will be on when the valve is operating n...

Page 16: ...tor is enabled with 1 1 Nxm 0 8 lb ft of torque and the valve closes If the flow demand source is configured for EGS CAN or Jenbacher CAN the valve reads the CAN ID input pins and begins sending diagn...

Page 17: ...urred for which there is a back up mode of operation possibly with reduced accuracy or performance If any warnings are active the status output is off Errors An error indicates a problem that prevents...

Page 18: ...e After any pressure adjustments ensure during normal operation that pre pressure and differential pressure are operating within the ranges specified in the General Specifications section of this manu...

Page 19: ...fault for Node Id 18 All others 384 Node Id Node ID 18 default address of TecJet when configured as TecJet 1 Data Byte 1 Actual Fuel Valve Position Data length 1 byte Resolution 0 4 bit 0 offset Multi...

Page 20: ...SYNC message COB Id 914 0x392 default for Node Id 18 All others 896 Node Id Range Boolean 8 bytes of status All reserved bits are set to 0 Data Length 8 bytes Byte 1 Overall Status Bit 0 OVERALL_STATU...

Page 21: ...e timeout for this message is adjustable from 10 to 10 000ms COB Id 530 0x212 default for Node Id 18 All others 512 Node Id Node ID 18 default address of TecJet when configured as TecJet 1 Data length...

Page 22: ...alve Position 18 1 T Byte 2 UINT8 Absolute Inlet Gas Pressure 18 1 T Bytes 3 4 UINT16 Absolute Outlet to Inlet Gas Pressure Differential 18 1 T Bytes 5 6 UINT16 Fuel Temperature 18 1 T Byte 7 UINT8 Ga...

Page 23: ...n Transmission repetition rate 100 ms TecJet 50 Plus Engine Control Data length 8 bytes Data Page 0 PDU format 255 PDU specific 252 Default priority 6 PGN 65532 0xFFFC Data Byte 1 Actual Fuel Valve Po...

Page 24: ...ameter Group Number 65535 0xFFFF Data Bytes 8 bytes of status Byte 1 Overall Status Bit 0 OVERALL_STATUS_OK Bit 1 RESERVED Bit 2 ZERO_PRESSURE_DETECTED Bit 3 ZERO_FLOW_DETECTED Bit 4 FLOW_NOT_REACHED...

Page 25: ...power has been applied to the TecJet 50 Plus if the TecJet is configured for the EGS 02 Flow Demand mode The Address Claimed message will be sent out in response to a Request for Address Claimed if t...

Page 26: ...claim current address Bus off Error occurred or collision detected POST Complete Send Address Claim Received a contending Address Claim No Contending Address Claim Received a contending Address Claim...

Page 27: ...Address 18 125 126 127 respectively See J1939 81 Section 4 1 1 9 Manufacturer Code Field Woodward Governor Industrial Controls 153 See J1939 81 Section 4 1 1 10 Position Hold Feature This feature sho...

Page 28: ...6065 mm 9 4 in See section on valve sizing for detailed information Weight 31 kg 68 lb Mounting See installation drawings Fuel connections Filter Requirements less than 50 0 m See outline drawing for...

Page 29: ...are allowed at high load operation assuming that the gas differential pressure requirements are still met Fuel gas differential pressure delta p should be between 70 and 275 mbar delta p below this r...

Page 30: ...atory Compliance European Compliance for CE Marking EMC Directive Certified to 89 336 EEC COUNCIL DIRECTIVE of 03 May 1989 on the approximation of the laws of the Member States relating to electromagn...

Page 31: ...the application outlet pressure is at sea level atmospheric pressure Take the increased flow rate value and the pressure drop value and determine where they cross on the graph This is the maximum flo...

Page 32: ...TecJet 110 Fuel Metering System Manual 26185 26 Woodward Figure 4 1 Maximum and Minimum Specialty Gas Flow Capacity of TecJet 110 50 Plus and 50...

Page 33: ...Manual 26185 TecJet 110 Fuel Metering System Woodward 27 Figure 4 2 Maximum and Minimum Natural Gas Flow Capacity of TecJet 110 50 Plus and 50...

Page 34: ...cessive pressure drop in fuel system Inlet gas pressure and or the pressure across the valve is too low pressure regulator problem Gas properties do not match used gas parameters The wrong size TecJet...

Page 35: ...equired Zero Flow Detected Flow demand source is PWM If the PWM flow demand high low warnings are not active the flow demand is zero If the PWM Flow Demand High or PWM Flow Demand Low warning is activ...

Page 36: ...The service tool displays the analog input current and the range limits CAN Flow Demand Failed The CAN flow demand is not being received The time between messages must be less than the CAN flow demand...

Page 37: ...high warning threshold Warning threshold improperly configured Pressure regulator adjusted too high Configure warning threshold for value appropriate to the application Adjust pressure regulator Delt...

Page 38: ...essure Sensor High The Fuel Gas Pressure sensor has failed to a high value The fuel gas pressure value is derived from the default downstream pressure table instead Internal fault Replace valve Fuel G...

Page 39: ...tion Check battery charger for correct operation Check wiring for correct size length contacts fuses PWM Flow Demand High The PWM flow demand exceeds the PWM flow demand maximum duty cycle fail limit...

Page 40: ...e or more of the errors below is active Internal Error The valve has detected an internal error that prevents it from operating Delta P Sensor High The delta P sensor has failed to a high value Delta...

Page 41: ...re product TecJet Tools Follow the installation instructions given on that page TecJet Users Guide After the service tool has been installed from the Windows Start menu select Programs then Woodward t...

Page 42: ...metry of the TecJet especially the valve plate or bore area around the valve plate will change the calibration of the valve and void the warranty High pressure washing is not recommended There are no...

Page 43: ...a around the valve plate for any remaining contamination Use a soft plastic brush or equivalent to gently remove any remaining contamination and rinse with tap water as necessary Remove the tubing fro...

Page 44: ...quipment system documentation for details Woodward Business Partner Support Woodward works with and supports a global network of independent business partners whose mission is to serve the users of Wo...

Page 45: ...advance of a scheduled outage to request a replacement control unit If the unit is available at the time of the call it can usually be shipped out within 24 hours You replace your field control unit w...

Page 46: ...ng materials when returning a complete control protective caps on any connectors antistatic protective bags on all electronic modules packing materials that will not damage the surface of the unit at...

Page 47: ...pment with which our products interface For information on these services please contact us via telephone email us or use our website and reference www woodward com support and then Customer Support H...

Page 48: ...gaseous steam etc Rating Application Control Governor Information Please list all Woodward governors actuators and electronic controls in your system Woodward Part Number and Revision Letter Control D...

Page 49: ...Manual 26185 TecJet 110 Fuel Metering System Woodward 43...

Page 50: ......

Page 51: ......

Page 52: ...t Drake Road Fort Collins CO 80525 USA Phone 1 970 482 5811 Fax 1 970 498 3058 Email and Website www woodward com Woodward has company owned plants subsidiaries and branches as well as authorized dist...