30
TD_PCM1x_Packages_Installation_09.04_GB
6 Technical
Data
Name
plate
------------------------------------------------------------------------------------------------------------------------------------------------------------------
1
S/N
serial number (numeric)
2
S/N
manufactured date (YYMM)
3
S/N
serial number (as Barcode)
4
P/N
item number
5
REV
item number revision
6
P/N+REV item revision (Barcode)
7
Type
description
8
Type
description (as Barcode)
9
Details
technical data
10
UL
UL sign
Measuring values, voltages ------------------------------------------------------------------------------------------------------------------------------------------------ /
∆
-
Measuring voltages
[1] 120 Vac
Rated value (Vn) ....................................... 69/120 Vac
Maximum
value
(V
L
max) ...........................max. 150 Vac
[4] 400 Vac
Rated value (Vn) ..................................... 231/400 Vac
Maximum
value
(V
L
max) ...........................max. 300 Vac
-
Setting range (prim) ...................................................................... 0.050 to 65.000 kVac
- Setting range (sec)
[1]
.......... 50 to 125 Vac .................
∆
50 to 114 Vac
[4]
.......... 50 to 480 Vac .................
∆
50 to 380 Vac
-
Measuring frequency ............................................................... 50/60 Hz (40.0-70.0 Hz)
-
Accuracy.......................................................................................................... Class 1
-
Input resistance per path.............................................................................. [1] 0.21 M
Ω
[4] 0.7 M
Ω
-
Maximum power consumption per path..............................................................< 0.15 W
Measuring
values,
currents
------------------------------------------------------------------------------------------------------------- galvanically isolated
-
Measuring current
[../1]
Rated value (In)......................................... ../1 A
[../5]
Rated value (In)........................................ ../5 A
-
Accuracy.......................................................................................................... Class 1
-
Linear measuring range
Generator (terminals x-x)..................................... 3.0 × In
Mains/ground current (terminals x/x) .................. 1.5 × In
-
Maximum power consumption per path..............................................................< 0.15 VA
-
Rated short-time current (1 s)
[..1/ A]........................................................ 50.0 × In
[../5 A]....................................................... 10.0 × In
Ambient
variables-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------
-
Power supply ......................................................................... 12/24 Vdc (9.5-32.0 Vdc)
-
Intrinsic consumption ..................................................................................... max. 20 W
-
Ambient temperature
Storage....................................
-
30-
+
80 °C /
-
22-
+
176 °F
Operation .................................
-
20-
+
70 °C /
-
4-
+
158 °F
-
Ambient humidity ........................................................................... 95 %, non condensing