5.9.2 Allocation of the Reset Functions
When setting of the parameters for the blocking function is completed you are in the allocation
mode for the reset functions. Whether the assigned relay should be reset manually or automatically
after activation or trip can be allocated to each of the activation or trip elements. Which of the reset
function
•
If necessary the reset function can be changed with <+> or <-> and saved with <ENTER>
Perhaps a password has to be entered.
•
Proceed to the next function with <SELECT/RESET>
•
After selection of the last reset function settings for the 2nd parameter set can follow.
•
For allocation of the output relays press push-button <SELECT/RESET> again. (See next
chapter).
•
Symbol
Protective Functions
Default
Setting
Possible Settings LED/Colour
ϑ
>
Overload warning
AUTO
HAND ; AUTO
ϑ
> red
I
B
> x k
Overload alarm
AUTO
HAND ; AUTO
I
B
>
green
I
B
> x k
Overload trip
AUTO
HAND ; AUTO
I
B
>
green/
τ
W
green
I<
Undercurrent alarm
AUTO
HAND ; AUTO
I< red
tI<
Undercurrent trip
AUTO
HAND ; AUTO
I< red/t> red
I>
Over current alarm
AUTO
HAND ; AUTO
I> red
tI>
Over current trip
AUTO
HAND ; AUTO
I> red/t> red
I>> Start
Short-circuit tripping when
starting*
AUTO
HAND ; AUTO
I>> rot/t> rot/ Start
green
I>> Start
Short-circuit tripping during
oper.
AUTO
HAND ; AUTO
I>>red
tI>>
Start/op.
Short-circuit tripping during
oper.
AUTO
HAND ; AUTO
I>> red/t> red
I2>
Load unbalance alarm
AUTO
HAND ; AUTO
I2> red
tI2>
Load unbalance trip
AUTO
HAND ; AUTO
I2> red/t> red
I
E
>
Earth current alarm
AUTO
HAND ; AUTO
I
E
> red
tI
E
>
Earth current trip
AUTO
HAND ; AUTO
I
E
> red/t> red
tCBFP
CB failure protection
AUTO
HAND ; AUTO
CB green
Trip
External trip
AUTO
HAND ; AUTO
Trip red
Table 5.4: Default setting of the Reset Functions
* Short-circuit excitation during starting always has automatic reset