Manual 37143A
MFR 15 - Protection Relay & Control
© Woodward
Page 107/119
Option
Parameter
Setting range
Default setting
Customer setting
G/GF/Y
Freq. controller
Dead band
0.02 to 1.00 Hz
0.10 Hz
..
Freq. controller
Time pulse>
10 to 250 ms
80 ms
G/GF/Y
Freq. controller
gain
0.1 to 99.9
10.0
G/Y
+QF
Pr-sensitivity Freq.
1 to 240
30
..
Reset time
Freq.
0.0 to 60.0 s
2.5 s
G/Y
+QF
Derivative act.
time (freq)
0.00 to 6.00 s
0.20 s
G/Y
Freq. controller
Droop
0.0 to 20.0 %
5.0 %
B
Power controller
ON/OFF ON
1
0
1
0
B+X..
External setp.
Adjustment
ON/OFF OFF
1
0
1
0
..
Analog input
0 to 20 mA / 4 to 20 mA
0 to 20 mA
0
4
0
4
..
External setp.
0 mA
0 to 32000 kW
000 kW
B+X
External setp.
20 mA
0 to 32000 kW
500 kW
B
Power controller
Setpoint
0 to 32000 kW
500 kW
..
Power controller
Ramp
0 to 100 %
50 %
..
Power limitation
P. max
10 to 120 %
100 %
..
Power controller
Dead band
0.1 to 25.0 %
2.5 %
..
Power controller
Sens.red.
1.0 to 9.9
2.0
..
Power controller
T.impuls >
10 to 250 ms
80 ms
..
Power controller
Gain
0.1 to 99.9
5.0
B
Power controller
Sens.red.
1.0 to 9.9
2.0
B
+QF
Pr.-sensitivity Power
1 to 240
30
..
Reset time
Power Tn
0.2 to 60 s
2.5 s
B
+QF
Deriv. act.time
Power Tv
0.0 to 6.0 s
0.20 s
B
Power reduction
Setpoint
5 to 110 %
15 %
B
Power reduction
Time
0 to 600 s
5 s
G/GU/Y
Volt. controller
ON/OFF ON
1
0
1
0
G/GU
Volt. controller
Setp.
variable / fixed
fixed
v
f
v
f
G/GU/Y
Volt. controller
Setpoint
50 to 125 V / 70 to 440 V
100 / 400 V
G/GU
Setpoint voltage
min. value
50 to 125 V / 70 to 440 V
90 / 360 V
..
Setpoint voltage
max. value
50 to 125 V / 70 to 440 V
1190 / 440 V
..
Setpoint voltage
Gradiant
1 to 20 V/S
2 V/S
G/GU
Setpoint voltage
Ramp
1 to 20 V/S
2 V/S
G/GU/Y
Volt. controller
Dead band
0.1 to 15.0 V / 0.5 to 60.0 V
3.0 V
..
Volt. controller
Sens.red.
1.0 to 9.9
2.0
..
Volt. controller Time pulse >
20 to 250 ms
80 ms
G/GU/Y
Volt. controller
Gain
0.1 to 99.9
10.0
G/Y
+QU
Pr-sensitivity Volt.
1 to 240
30
..
Reset time
Volt.
0.0 to 60.0 s
2.5 s
G/Y
+QU
Derivative act.
time (Volt)
0.00 to 6.00 s
0.20 s
G/GU/Y
Volt. controller
Droop
0.0 to 20.0 %
5.0 %
C
Power-factor controller
ON/OFF ON
1
0
1
0
C
+G/GU
Pow.fact.contr. Setp.
variable / fixed
fixed
v
f
v
f
C
Pow.fact.contr. Setpoint
i0.70 to 1.00 to c0.70
1.00
C
+G/GU
Setp. pow.fact.
min. value
i0.70 to 1.00 to c0.70
c0.80
..
Setp. pow.fact.
max. value
i0.70 to 1.00 to c0.70
i0.80
..
Setp. pow.fact.
Gradiant
0.01 to 0.30 /s
0.05 /s
C
+G/GU
Setp. pow.fact.
Ramp
0.01 to 0.30 /s
0.05 /s
C
Pow.fact.contr. Dead
band
0.5 to 25.0 %
2.5 %
..
Pow.fact.contr. Sens.red.
1.0 to 9.9
2.0
..
Pow.fact.contr.
Time pulse >
20 to 250 ms
80 ms
C
Pow.fact.contr. Gain
0.1 to 99.9
5.0
C
+QU
Pr.-sensitivity Pow.f.
1 to 240
30
..
Reset time
Pow.f.
0.2 to 60 s
2.5 s
C
+QU
Derivative act.
time (cos)
0.0 to 6.0 s
0.20 s
B/W/O
Stop sequence
ON/OFF ON
1
0
1
0
B/W/O
Stop sequence
Ramp
1 to 100 %/s
5 %/s
W
Active power
Load share
ON/OFF ON
1
0
1
0
W
Act. load share
Frequency
10 to 99 %/s
50 %
O
Reactive power
Load share
ON/OFF ON
1
0
1
0
O
React.load share
Voltage
10 to 99 %/s
50 %