background image

Manual 37140A 

MFR 11 - Protection Relay 

 

 

 

 

Page 52/80 

© Woodward 

Analog Outputs (

Options A1/2/3/4/6/8

≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡

 

 

 

NOTE

 

The common use of the analog outputs, the interfaces and the discrete inputs depends on their re-
spective combinations. Please pay attention to the combinations possible as described in the intro-
duction.

 

 
 

 

 

CAUTION 

The function of the analog outputs is restricted during configuration via the side connector (ver-
sion 3.xxx). The parameter "Direct parametr." must be set to "NO" in order to make all analog outputs 
available (refer to "Direct Configuration (from Version 3.0xx)" on pa
ge 34).

 

 
 
It is possible to configure a linear measuring range for each analog output and assign it to a specific measured 
value (refer to Table 6-3). The -20/0/4 to 20 mA analog outputs may be configured as a -20 to 20 mA, 0 to 
20 mA, or 4 to 20 mA output. The -10/0 to 10 V analog outputs may be configured as a -10 to +10 V or 0 to 
+10 V output. The user may define the upper and lower limits of the analog input measuring range. Text may be 
assigned to the input as well. 
 

 

Value 

Lower and upper setting value 

 

0 V, -10 V 

0 mA, 4 mA, -20 mA 

10 V, 20 mA 

V L1-N

 

0 to 65,000 V

 

V L2-N

 

0 to 65,000 V 

V L3-N

 

0 to 65,000 V 

V L-N mean value 

0 to 65,000 V 

V L-N max. value 

0 to 65,000 V 

V L-N min value 

0 to 65,000 V

 

V L1-L2 

0 to 65,000 V 

V L2-L3 

0 to 65,000 V

 

V L3-L1 

0 to 65,000 V 

V L-L mean value 

0 to 65,000 V 

V L-L max. value 

0 to 65,000 V 

V L-L min. value 

0 to 65,000 V 

Frequency 

40.00 to 80.00 Hz 

 

Table 6-3: Analog outputs, table of values 

 

Summary of Contents for MFR 11

Page 1: ...37140A Manual Version 3 xxxx Manual 37140A MFR 11 Protection Relay...

Page 2: ...ff before disconnecting the battery from the system Electronic controls contain static sensitive parts Observe the following precautions to prevent dam age to these parts Discharge body static before...

Page 3: ...1 Wiring Diagram Optional Models 100 Vac and 400 Vac 11 Wiring Diagram Optional Models 690 Vac 12 Power Supply Standard 13 Wide Range Power Supply Option N 13 Measuring Inputs 14 Voltage 14 Discrete I...

Page 4: ...to Acknowledgement of the Relays 48 Auto Acknowledgement of Messages 49 Changing the Relay Assignment Relay Manager Standard Option R 50 Analog Outputs Options A1 2 3 4 6 8 52 Interface Options SU SB...

Page 5: ...e 5 80 APPENDIX F SERVICE OPTIONS 75 Product Service Options 75 Returning Equipment for Repair 75 Packing a Control 76 Return Authorization Number RAN 76 Replacement Parts 76 How to Contact Woodward 7...

Page 6: ...Figure 3 8 Discrete inputs 16 Figure 3 9 Relay outputs 16 Figure 3 10 Analog outputs 17 Figure 3 11 Interfaces 18 Figure 3 12 Interface CAN bus shielding 18 Figure 3 13 Interfaces CAN bus topology 19...

Page 7: ...ut if the described function is standard or has to be ordered optionally Mounting B Flush mounting M DIN rail rear panel mounting Hardware variation non standard models e g additional relays Current t...

Page 8: ...is meas ured three phase if the measured voltage exceeds 15 of the nominal voltage This ensures rapid and precise measurement of the frequency However the frequency is still measured correctly even i...

Page 9: ...20 0 4 to 20 mA A6 8 Analog outputs 10 0 to 10 V A8 Interface uni directional SU Interface bi directional SB Interface CAN bus incl remote control SF Wide range power supply 90 to 265 Vac dc N 9 9 9 R...

Page 10: ...igarette packages cello phane wrappers vinyl books or folders plastic bottles etc away from the control modules and work area as much as possible 4 Opening the control cover may void the unit warranty...

Page 11: ...version 3 0xx 100 400 V model A1 Relay 2 Relay 1 Relay 3 Option Yc Synchro Check Standard Analog output 1 Common 1 2 2003 03 24 MFR 11 Wiring Diagram r13ww 1303 ap skf 12 11 10 9 50 51 0 13 16 15 14 2...

Page 12: ...output 5 A2 A8 A4 A6 A3 A8 Analog output 3 Analog output 2 Analog output 1 Analog output 4 Analog output 3 Common 3 4 Analog output 4 Analog output 8 Analog output 7 Analog output 6 Analog output 5 Co...

Page 13: ...mm AWG mm AWG mm AWG mm AWG mm 30 0 05 21 0 38 14 2 5 4 25 3 0 95 600MCM 300 28 0 08 20 0 5 12 4 2 35 4 0 120 750MCM 400 26 0 14 18 0 75 10 6 1 50 300MCM 150 1000MCM 500 24 0 25 17 1 0 8 10 1 0 55 350...

Page 14: ...ng voltage L2 2 5 mm 3 Measuring voltage L3 2 5 mm 4 400V direct or trans former 100V Neutral point of the 3 phase system transformer 2 5 mm 690 V version Measuring voltage L3 L2 L1 N G 3 4 5 6 L3 L2...

Page 15: ...nnected minor inaccuracies will occur during the three phase power measurement Functionality will not be affected if the voltage L3 is not con nected and the power measurement is configured as single...

Page 16: ...ax A B 5 6 Blocking of protective functions remote acknowl edgement not in the 690 V version 2 5 mm Outputs Relay Outputs Standard Option R A B Relay output Relay output external device external devic...

Page 17: ...Analog output 1 Option A2 3 6 1 5 mm 53 52 Analog output 2 Option A3 6 1 5 mm 55 54 Analog output 3 Option A3 6 1 5 mm 82 81 Analog output 4 Option IK No 1 Option A6 1 5 mm 84 83 Analog output 5 Optio...

Page 18: ...tter drives the current RxD RxD TxD TxD Termination NC GND CAN H CAN L D A B C Interface Profi bus DP Screen A Line GND 5 V E F B Line RTS Figure 3 11 Interfaces Terminal Description A X1 B X2 C X3 D...

Page 19: ...T structure bus is utilized stub end feeders or branch lines are not recommended CAN L and CAN H are interchanged Not all devices on the bus are using identical Baud rates Terminating resistor s is ar...

Page 20: ...nes like phone lines will destroy the unit CAUTION The connection cable delivered with the DPC must be used between DPC and the unit to ensure proper functionality of the unit An extension or utilizat...

Page 21: ...ny potential source The following protective functions cannot be blocked via this discrete input Overvoltage monitoring Overfrequency monitoring Zero voltage monitoring External acknowledgement of the...

Page 22: ...pe change over contact The relay manager controls this relay If the Option YC is installed the synch check function is assigned to this relay Option R Relay 4 to 7 Terminal 19 through 30 Output relay...

Page 23: ...phase shift Option V Ph shift df dt ROCOF Option D Fault df Table 4 1 Alarms Alarm Acknowledgement A fault alarm is indicated by the Alarm LED By pressing the Clear button the active faults are ackno...

Page 24: ...iguration cable there DPC MFR 1 L2 L23 L1 L12 L3 L31 Hz Reversible Display Operating Display Menu Digit Cursor Clear Alarm Converting Controlling Monitoring Select 14 1 2 13 12 4 3 5 7 6 Figure 5 1 Fr...

Page 25: ...Indication of the delta voltages If this LED is illuminated the values indicated on the display are the delta voltages phase phase 3 Operation Color Green Operation This LED is illuminated constantly...

Page 26: ...ved by pressing the Select push button once By pressing the button again the user causes the system to advance to the next configuration screen 13 Menu Digit Color none Menu Digit Automatic mode Menu...

Page 27: ...system are indicated If the application is a three wire system the configuration screen Volt Measuring must be configured to phase to phase The Wye LED will not illuminate in this application The Wye...

Page 28: ...a list of all alarm messages that the control may monitor for depending on how the unit is configured Alarm type Alarm text Overvoltage level 1 Option U Overvolt 1 Overvoltage level 2 Option U Overvol...

Page 29: ...tor to reverse up to four previous screens exception it is not possible to reverse from the first parameter to the last parameter To perform the reverse function through the parameter screens the Sele...

Page 30: ...ble to activate it only after setup is complete SEQUENCE DIAGRAM on the following page By entering a five character code number the input operation can be protected from unauthorized access opera tion...

Page 31: ...O the code is inquired again Leaving the inquiry is only possible by terminating input mode Code no 000 New code Code for seal 001 new entry 00000 to 60000 After breaking the old seal the unit request...

Page 32: ...to CS0 thus locking the device for external persons If for 2 hours uninterruptedly supply voltage is applied the device automatically switches to code level 0 NOTE Starting with Version 2 1xx 3 1xx Th...

Page 33: ...1 password 0000 to 9999 This screen appears only when the level 2 password has been entered After enter ing the digits into this screen the code level for level 1 basic service level is set After ente...

Page 34: ...ogram has been started establish the communication by pressing the F2 button This will es tablish a data link between the unit and the laptop PC Start the sub program Device Parameterization and adjus...

Page 35: ...t appear Potential Transformer Configuration NOTE The screens described below are not available in the 690 V versions Units without Option YC Volt transformer secondary 000V Potential transformer seco...

Page 36: ...in the display For voltages measured without a potential transformer secondary and primary voltage must be configured the same Volt transformer prim MN 00 000kV Mains potential transformer primary 00...

Page 37: ...ant due to the inherent delay of the breaker regardless of the fre quency differential of the two systems If the voltage and frequency differential of the two systems are within permissible limits the...

Page 38: ...e differential 0 1 to 15 0 A close command will not be issued until the measured differential voltage of the two systems is less than value configured here An internal hysteresis of 12 5 of the value...

Page 39: ...e earth fault in a compensated or isolated mains resulting in the voltage protec tion tripping The only effect on the screen Voltage measuring is the one de scribed in the above note The settings in t...

Page 40: ...e must ex ceed and remain above the configured threshold without interruption for at least the period of time specified in this screen Screen for Phase neutral Overvoltage 2 Phase N 000V Screen for Ph...

Page 41: ...all below and remain below the configured threshold without interruption for at least the period of time specified in this screen Screen for Phase neutral Undervoltage 2 Phase N 000V Screen for Phase...

Page 42: ...1 2 to 87 V 4 6 to 300 V The threshold for detecting a zero voltage condition is defined by this parameter If this limit is reached or fallen below the unit does not display a message If a relay was a...

Page 43: ...layed Asymmetry Response v 00V Maximum permissible asymmetry 0 to 99 V The maximum voltage asymmetry is defined by this parameter If this limit is reached or exceeded the unit outputs the message Asym...

Page 44: ...gized Overfrequency 1 Delay 00 00s Pickup delay level 1 0 02 to 99 98 s In order to initiate an overfrequency level 1 alarm the measured frequency must exceed and remain above the configured threshold...

Page 45: ...derfrequency 1 Delay 00 00s Pickup delay level 1 0 02 to 99 98 s In order to initiate an underfrequency level 1 alarm the measured frequency must fall below and remain below the configured threshold w...

Page 46: ...itoring is disabled and the subsequent screens of this function are not displayed Phase jump monit Vector phase shift monitoring one three phase 3 phase only one three phase An alarm will be issued if...

Page 47: ...suppressed with the discrete input Blocking of protective functions remote acknowledgement df dt Monitoring ON df dt monitoring ON OFF ON Rate Of Change Of Frequency monitoring is enabled The subse q...

Page 48: ...with the discrete input Blocking of protective functions remote acknowledgement are only reset after the fault condition is no longer present Auto clearing Relays configured ON refer to Auto Acknowle...

Page 49: ...Option U Overvolt Overvoltage level 1 and 2 Undervoltage Option U Und volt Undervoltage level 1 and 2 Asymmetry Option U Asymmetry Overfrequency Option U Overfreq Overfrequency level 1 and 2 Underfre...

Page 50: ...e assigned monitoring function has tripped R The relay is configured as normally closed N C contacts The relay is always energized and will only de energize release if the as signed monitoring functio...

Page 51: ...h Option R has a protective function that us required to output a signal to relays 2 4 and 7 That protective function relay assignment should be configured as 2470 The sequence of the num bers has no...

Page 52: ...og output and assign it to a specific measured value refer to Table 6 3 The 20 0 4 to 20 mA analog outputs may be configured as a 20 to 20 mA 0 to 20 mA or 4 to 20 mA output The 10 0 to 10 V analog ou...

Page 53: ...F The analog output is not enabled The subsequent screens of this function are not displayed The only variable that may be changed for this parameter is the lower value for this analog output The uppe...

Page 54: ...ta word RK512 0 to 255 Data word address in receiver e g PLC Screens for Protocol Profibus DP Slave Option SU Device number Profibus 000 Device number profi bus DP slave 0 to 126 Device number for the...

Page 55: ...ID 802 etc Device number CAN Bus 0 Device number CAN bus 1 to 8 The device number at CAN bus is entered here The device number affects the cal culation of the transmitting and controlling IDs Baudrate...

Page 56: ...bits are not read within the prescribed time and unsuccessful data exchange is detected and the alarm message Interface is is sued OFF The interface monitoring is disabled Interface fault to relay 000...

Page 57: ...nected in correct phase sequence The connect command for the unit circuit breaker must be disconnected at the unit circuit breaker The field rotation must be monitored for proper rotation Any absence...

Page 58: ...code number 0 to 9999 On accessing the parameterization mode a code number which identifies the vari ous users is first requested The indicated number XXXX is a random number ZU and is confirmed usin...

Page 59: ...r1ww 0503 ab skf 70 75 45 16 32 17 50 130 96 8 90 130 72 65 27 35 61 50 40 1 70 75 45 16 32 17 X5 X1 Option S Option A6 A8 Back view with connecting terminals Bottom view Back plate mounting optional...

Page 60: ...ground 1 150 Vac 4 300 Vac 7 400 Vac Rated surge voltage 1 2 5 kV 4 4 0 kV 7 4 0 kV Measuring frequency 40 0 to 80 0 Hz Accuracy Class 1 Resistance 0 1 Linear measuring range 1 3 Vrated Input resista...

Page 61: ...ng Screw type terminals depending on connector 1 5 mm 2 5 mm or 4 mm Recommended tightening torque 1 5 mm 2 5 mm 0 5 Nm 4 mm 0 6 Nm use 60 75 C copper wire only use class 1 wire only or equivalent Wei...

Page 62: ...ltage VL1 VL2 VL3 VL12 VL23 VL31 0 to 520 V 0 to 65 kV 1 Accuracy depending on the configured transformer ratio Reference conditions The data apply to the following reference conditions Input voltage...

Page 63: ...Power factor cosphi dim less 100 Internal 24 25 13 26 27 MUX 5 1 12 Real power kW Internal 26 27 14 28 29 MUX 5 2 13 Reactive power kvar Internal 28 29 15 30 31 MUX 5 3 14 Busbar voltage L12 V Option...

Page 64: ...Bit 1 1 Bit 0 0 Vector phase jump 44 45 23 46 47 MUX 8 2 22 Internal alarms 3 Bit 15 1 Bit 14 0 Internal Bit 13 1 Bit 12 0 Internal Bit 11 1 Bit 10 0 Internal Bit 9 1 Bit 8 0 Internal Bit 7 1 Bit 6 0...

Page 65: ...0 Internal Bit 5 1 Bit 4 0 Internal Note example bit 15 14 Bit 3 1 Bit 2 0 Internal 0 1 alarm not triggered 1 0 alarm triggered Bit 1 1 Bit 0 0 Internal NOTE Watchdog functions which are not available...

Page 66: ...control line RTS to ON The prerequisite of this is that no data are received CTS OFF The receiver regis ters this status and indicates its readiness to receive by switching its RTS line to ON The tra...

Page 67: ...a telegram of 7 Bytes is expected which is structured as follows all word vari ables are in the high byte low byte format Byte 1 Multiplexer Byte 2 3 1 data word note table no 1 multiplexed MUX 1 1 By...

Page 68: ...t Byte 1 The bit 0 is used as a watchdog If monitoring is switched ON in the configuration screen this bit must be toggle every 4 seconds The unit monitors this and possibly triggers a fault and reini...

Page 69: ...Y N MEASUREMENT Volt Measuring Phase to phase Phase neutral Phase neutral pp pn pp pn Volt transformer secondary 50 to 125 50 to 480 V 100 400 V Volt transformer primary 00 100 to 65 000 kV 00 400 kV...

Page 70: ...B1 G3 UN Zero voltage V ph ph 3 to 180 V 12 to 520 V Phase N 2 to 87 V 6 to 300 V Zero voltage Delay 0 02 to 99 98 s 0 25 s Zero voltage Hysteresis 0 to 99 V 1 4 8 V UN Release delay Zerovolt 0 02 to...

Page 71: ...N OFF ON 1 0 1 0 Clearing display after 1 to 99 s 1 s Change relay allocation YES NO YES Y N Y N YC Funct relay 12 R release E R RE Funct relay 123 R release E R REE R Funct relay 45 R release E R EE...

Page 72: ...st of parameters 400 V Analog output 3 OFF 20 to 20mA 0 to 20 mA 4 to 20 mA 20 to 20mA OFF 20mA 0 20mA 4 20mA OFF 20mA 0 20mA 4 20mA A3 6 A4 8 OFF 10 to 10 V 0 to 10 V 10 to 10V OFF 10V 0 10V OFF 10V...

Page 73: ...rameters 230 V Analog output 8 OFF 20 to 20mA 0 to 20 mA 4 to 20 mA 20 to 20mA OFF 20mA 0 20mA 4 20mA OFF 20mA 0 20mA 4 20mA A8 OFF 10 to 10 V 0 to 10 V 10 to 10V OFF 10V 0 10V OFF 10V 0 10V Analog ou...

Page 74: ...N 0 to 65 000 V V L3 N 0 to 65 000 V V L N mean value 0 to 65 000 V V L N max value 0 to 65 000 V V L N min value 0 to 65 000 V V L1 L2 0 to 65 000 V V L2 L3 0 to 65 000 V V L3 L1 0 to 65 000 V V L L...

Page 75: ...your problem can be resolved over the phone If not you can select which course of action you wish to pursue based on the available services listed in this section Returning Equipment for Repair If a c...

Page 76: ...ent in Stuttgart 49 711 789 54 0 They will help expedite the processing of your order through our distributors or local service facility To expedite the repair process contact Woodward in advance to o...

Page 77: ...wing international Woodward facilities to obtain the address and phone number of the facility nearest your location where you will be able to get information and service Facility Phone number USA 1 97...

Page 78: ...free or local phone numbers e mail us or use our website and refer ence technical support Product Training is available on site from several of our worldwide facilities at your location or from GE Glo...

Page 79: ...__________ Control see name plate Unit no and Revision P N ___________________ REV ____________ Unit type MFR 11 ___________________________________ Serial number S N _________________________________...

Page 80: ...e 29 70565 Stuttgart Germany Phone 49 711 789 54 0 Fax 49 711 789 54 100 stgt info woodward com Homepage http www woodward com power Woodward has company owned plants subsidiaries and branches as well...

Reviews: