Manual 37351A
MFR 11 Packages - Protection Relay
© Woodward
Page 53/59
Pkg.
Parameter
Setting range
100/400/690 V
Default setting
Customer setting
RELAY CONFIGURATION
External Clearing
ON/OFF ON
1
0
1
0
Auto-clearing Relays
ON/OFF ON
1
0
1
0
Release delay
Overvoltage
0.02 to 99.98 s
0.10 s
Release delay
Undervoltage
0.02 to 99.98 s
0.10 s
Release delay
Asymmetry
0.02 to 99.98 s
0.10 s
SC
SC+N
Release delay
Zerovolt.
0.02 to 99.98 s
0.10 s
Release delay
Overfreq.
0.02 to 99.98 s
0.10 s
Release delay
Underfrq.
0.02 to 99.98 s
0.10 s
VDEW
G59
G59N
Release delay
Phase jmp
0.02 to 99.98 s
0.10 s
G59
G59N
Release delay
df/dt
0.02 to 99.98 s
0.20 s
Auto-clearing Display
ON/OFF ON
1
0
1
0
Clearing display
after
1 to 99 s
1 s
Change relay-
allocation
YES/NO YES
Y
N
Y
N
SC
SC+N
Funct. relay 12
(R=release)
E/R RE
Funct. relay 123
(R=release)
E/R REE
G59
G59N
Funct. relay 45
(R=release)
E/R EE
G59
G59N
Funct. relay 678
(R=release)
E/R EEE
SC
SC+N
2. Synch.Check
relay 2
ON/OFF OFF
1
0
1
0
Overvoltage 1
to relay
0 to 2/3/8
0002
Overvoltage 2
to relay
0 to 2/3/8
0002
Undervoltage 1
to relay
0 to 2/3/8
0002
Undervoltage 2
to relay
0 to 2/3/8
0002
SC
SC+N
Zero-voltage to
relay
0 to 2/3/8
0002
Asymmetry to
relay
0 to 2/3/8
0002
Overfrequency 1
to relay
0 to 2/3/8
0003
Overfrequency 2
to relay
0 to 2/3/8
0003
Underfrequency 1
to relay
0 to 2/3/8
0003
Underfrequency 2
to relay
0 to 2/3/8
0003
VDEW
G59
G59N
Phase jump
to relay
0 to 2/3/8
0003
G59
G59N
df/dt to
relay
0 to 2/3/8
0003
Collect Response
to relay
0 to 2/3/8