Field Parameters
Field Parameters – Phase Differential Current
Parameter
Description
Setting range
Default
Menu path
Ib reference
Defines, which CT of device side
(local/remote) is uesd as reference Ib for
percentage-phase-differential-protection.
This setting becomes important only, if
different CT ratios at local and remote side
are used.
CT Local,
CT Remote
CT Local
[Field Para
/General
Settings]
Id Cutoff Level
The Differential Current shown in the
Display or within the PC Software will be
displayed as zero, if the Differential Current
falls below this Cutoff Level. This parameter
has no impact on recorders.
0.0 - 0.100In
0.005In
[Device Para
/Measurem
Display
/Diff]
IS Cutoff Level
The Restraint Current shown in the Display
or within the PC Software will be displayed
as zero, if the Restraint Current falls below
this Cutoff Level. This parameter has no
impact on recorders.
0.0 - 0.100In
0.005In
[Device Para
/Measurem
Display
/Diff]
460
MCDLV4
DOK-HB-MCDLV4-2E
Summary of Contents for HighPROtec MCDLV4
Page 3: ...Order Code Order Code 3 MCDLV4 DOK HB MCDLV4 2E...
Page 47: ...Installation and Connection 47 MCDLV4 DOK HB MCDLV4 2E...
Page 164: ...Input Output and LED Settings 164 MCDLV4 DOK HB MCDLV4 2E...
Page 433: ...Parameters 433 MCDLV4 DOK HB MCDLV4 2E...
Page 457: ...Device Parameters 457 MCDLV4 DOK HB MCDLV4 2E...
Page 473: ...Blockings 473 MCDLV4 DOK HB MCDLV4 2E...
Page 988: ...Protective Elements 988 MCDLV4 DOK HB MCDLV4 2E P P Q P Q P Q Q Q P S S...
Page 989: ...Protective Elements 989 MCDLV4 DOK HB MCDLV4 2E Pr Q P Q P Qr...
Page 1023: ...Protective Elements 1023 MCDLV4 DOK HB MCDLV4 2E...