5 Operation
5.1 Front panel
Fig. 14 shows the front panel of the easYlite-200 device.
Fig. 14: Front panel easYlite-200
It consists of:
1 - 16 LED lamps
2 - Labels for lamp-signal names
3 - Lamp test button
4 - Acknowledge button
5 - Communication status lamp
The LED lamps 1 represent 16 signal outputs from an easYgen
device, configurable as described in
Configuration and Labelling” on page 22. These may show various
operational/parameter states of the easYgen device or the con‐
trolled apparatus (circuit breakers, engine), display warnings or
alarms. The signalling for partcular lamps is further differentiated
by color (red, green, yellow) and lighting pattern (flashing, contin‐
uous).
The control button 3 ( ) is the lamp test button. All the lamps on
the LED panel will be illuminated yellow upon long-pressing this
button.
The control button 4 ( ) is the acknowledge button. By depressing
this button, the flashing lamp on the LED panel can be changed to
continuously illuminated and the horn signal from the genset con‐
trol can be silenced.
When the easYlite-200 is powered up, the communication status
lamp is illuminated green, while the remaining LEDs - yellow for a
short time (less than a second).
The communication bus status is indicated by the status lamp 5.
LED lamps
LED Buttons
Operating the easYlite-200
Operation
Front panel
37903A
easYgen Expansion Module | LED Lamp Expansion Module
26
Summary of Contents for easYlite-200