6.5.2
Changing Parameter Settings
6.5.2.1
Parameter Setting
The example tables below are excerpts. Refer to the following chapters for the complete
parameter lists:
•
•
•
╚═▷ “4.6 Configure Measurement”
•
Be sure to enter the password for the code level that is needed to get access for
changing parameter settings via the preferred interface.
The new entered value must comply with the parameter setting range when changing
the parameter setting.
Example 1: Addressing the generator rated voltage
ID
Parameter
Setting range
Data type
1766
Generator rated voltage
50 to 650000 V
UNSIGNED 32
☼
Example
• Modbus address = 40000 + (Par. ID + 1) = 41767
•
• Modbus length = 2 (UNSIGNED 32)
•
⚙
1. ▷
Fig. 304:
Modscan32 at address 41767
Set the configuration to address parameter 1766 as shown in
.
801
easYgen-3000XT Series
B37574
6 Application Field
6.5.2 Changing Parameter Settings
Released