ID
Parameter
CL
Setting range
[Default]
Description
8902
Show engine coolant
Temp.
2
[Yes]
No
Display of engine coolant
temperature on home screen.
4.3.3
Lamp Test
All lights on the controller may be tested for correct operation with this function.
[Parameter / Lamp test]
Lamp test is available via HMI/display, ToolKit, and parameter 10773 with logical
command variable 04.61.
4.3.4
Enter Password
General notes
The controller utilizes a password protected multi-level access hierarchy to prevent
unauthorized access to parameters, configuration and calibration items. This permits
varying degrees of access to the parameters being granted by assigning unique
passwords to designated personnel.
Password protection covers direct and remote access through all methods and interfaces
of interconnectivity of the device.
Personal security
Configure password security before handing over the device to the customer!
Note your password on a secure location. The next higher password level (2 and 4)
allows to reset the password of the level below (1 and 3).
To restore the according User Name Account needs support from Woodward (authorized
partner).
Access via channel ...
The following table and drawing provide an overview about the possible access channels
to the easYgen-XT.
Access to the easYgen-XT by a/an ...
below
HMI on the control directly
①
PC running ToolKit servlink, connected over USB
②
176
easYgen-3000XT Series
B37574