5. ▷
Fig. 230:
LogicsManager function "Flag 4"
Configure the LogicsManager function "Flag 4" as shown in (
).
6. ▷
Fig. 231:
LogicsManager function "Flag 5"
Configure the LogicsManager function "Flag 5" as shown in (
).
6.3.5
Performing Remote Start/Stop And Acknowledgment
The easYgen controller may be configured to perform start/stop/shutdown/
Acknowledgment functions remotely through the CAN bus or Modbus. The required
procedure is detailed in the following steps.
for a detailed description of the navigation through
the various display screens.
A detailed description of the individual parameters may be found in
Operation Mode AUTO - Automatic Run”
Be sure to enter the password for code level 2 or higher to be able to access the required
configuration screens.
Refer to ToolKit Manual for a description of the installation, configuration and usage of
the ToolKit visualization and configuration application.
Preliminary Conditions
We recommend to reset the unit to factory settings before proceeding.
for reference.
The LogicsManager factory settings are shown in
710
easYgen-3000XT Series
B37574
6 Application Field
6.3.5 Performing Remote Start/Stop And Acknowledgment
Released