![Woodward 1502ES Troubleshooting Manual Download Page 19](http://html1.mh-extra.com/html/woodward/1502es/1502es_troubleshooting-manual_995874019.webp)
Manual 36541
Solenoid Troubleshooting Guide
Woodward
15
Table 1B. Coil Resistance
Internally Switched Solenoids
Measurement Range Between
Pos (+) and Neg (-) Terminals
Model
No.
Voltage
Pull Coil Resistance
Hold Coil Resistance
12
0.359-0.438
15.28-18.67
24
1.350-1.650
89.10-108.90
32
2.466-3.014
145.35-177.65
48
4.563-5.577
359.73-439.67
1502
64
7.884-9.636
394.65-482.35
12
0.261-0.319
14.13-17.27
24
0.977-1.193
58.90-71.98
1504
36
2.430-2.970
114.12-139.48
12
0.232-0.284
9.82-12.00
24
0.878-1.073
46.55-56.89
1751
36
6.363-7.777
226.26-276.54
12
24
0.324-0.396
1.208-1.477
12.97-15.85
54.72-66.89
1753
64
8.730-10.670
296.10-361.40
12
0.195-0.239
10.04-12.27
1755
24
0.754-0.922
47.94-58.60
12
0.248-0.303
17.48-21.36
2001
24
0.936-1.144
71.01-86.81
12
0.179-0.219
13.33-16.29
2003
24
0.577-0.706
48.78-59.62
12
0.185-0.227
6.50-7.94
24
0.703-0.859
37.27-45.55
24
0.496-0.606
18.90-23.10
12
0.185-0.227
6.50-7.94
24
0.703-0.850
37.27-45.55
2370
24
0.358-0.438
23.98-19.62