It  must  be  verified  that  electric  supply  is  corresponding  to  the  unit  electric  nominal  data                        
(tension, phases, frequency) reported on the label in the front panel of the unit. 
Power connections must be made using a three-wire cable + neutral wire + ground cable. 
 
 

 
 
 
 
 

 
 
 
 
 
 

 

 
 
 
 
 

 
 
 

  
Ground connection is compulsory. Installer must connect ground cable with a dedicated terminal on 
the apposite terminal block. 
 

 

Close to the unit a main switch must be present. 

 

 

 

Power  cable  and  line  protection  must  be  sized  according  norm  and  laws  according 
with absorbed current of the machine (see technical data). 
 

 

 

The line voltage fluctuations must not be more than ±5% of the nominal value, while 
the voltage unbalance between one phase and another must not exceed 2%. If those 
tolerances  should  not  be  respected,  please  contact  our  Firm  to  provide  proper 
devices. 
 

 

 

Electric  supply  must  be  in  the  limits  shown:  in  the  opposite  case  warranty  will 
terminate immediately. 

 

 

 

Electrical  connections  therefore  must  be  always  done  according  to  the  instructions 
reported on the wiring diagram enclosed with the unit and norms and laws. 

 

 

 