9
Cooling
4. Pipe sizing
Pipework runs up to a maximum of 30m (total equivalent length) are recommend between the BMOP and BMIEP units. Each instal-
lation must be evaluated for the total equivalent pipe run length, including equivalent lengths for bends, additional fittings and
vertical lifts etc. Please refer to the appropriate interconnecting pipe sizing chart (tables below) for a full selection.
Using interconnecting pipe sizing charts
The pipework sizes below are based on the nominal duty of the BMIEP and BMOP combination, as shown in the tables. Pipework
should be selected based on the total equivalent run length of the interconnecting pipework between the two units, and not just
the dimensional length. Equivalent lengths for all bends, piping components and vertical rises should be added to the basic run
lengths to achieve the total equivalent run lengths. When using the tables to determine pipe length, round up the equivalent
length and do not interpolate between values. For example, if the pipe run is between 10m and 20m, always use the 20m values.
Cellar temperature 10°C
Evaporator bracket centres
CONDENSING UNIT
EVAPORATOR
UNIT
CELLAR TEMPERATURE 10
O
C
MODEL
UNIT CONN
MODEL
10m
20m
30m
SUCTION
LIQUID
SUCTION
LIQUID
SUCTION
LIQUID
SUCTION
LIQUID
BMOP-130-1
3/4“
3/8“
BMIEP-448-37
5/8"
3/8"
5/8"
3/8"
3/4"
3/8"
BMOP-150-1
3/4“
3/8“
BMIEP-448-48
5/8"
3/8"
3/4"
3/8"
3/4"
3/8"
BMOP-190-1
3/4“
3/8“
BMIEP-448-48
5/8"
3/8"
3/4"
3/8"
3/4"
3/8"
BMOP-210-1
7/8“
1/2“
BMIEP-448-48
5/8"
3/8"
3/4"
3/8"
7/8"
3/8"
BMOP-210-1
7/8“
1/2“
BMIE-448-69
5/8"
3/8"
3/4"
3/8"
7/8"
3/8"
BMOP-210-1
7/8“
1/2“
BMIEP-448-89
3/4"
3/8"
3/4"
3/8"
7/8"
1/2"
BMOP-250 -1/3
7/8“
1/2“
BMIEP-448-89
3/4"
3/8"
3/4"
3/8"
7/8"
1/2"
BMOP-320-1/3
7/8“
1/2“
BMIEP-448-89
3/4"
3/8"
7/8"
1/2"
1.1/8"
1/2"
BMOP-350-3
7/8“
1/2“
BMIEP-448-89
7/8"
3/8"
7/8"
1/2"
1.1/8"
1/2"
BMOP-360-3
7/8“
1/2“
BMIEP-448-133
7/8"
1/2"
1.1/8"
1/2"
1.1/8"
1/2"
Summary of Contents for Beermaster Plus BMIE-448-69
Page 1: ...wolseley co uk climate Beermaster Plus Cooling Range Installationand maintenanceinstructions...
Page 26: ...Cooling 26 23 Sales outlines BMOP130 BMOP250...
Page 27: ...27 Cooling BMOP 320 350 360...
Page 32: ...Cooling 32 BMOP 1PH BMO PLUS 1PH Schem Rev1...
Page 33: ...33 Cooling BMOP 3PH BMO PLUS 3PH Schem Rev1...
Page 34: ...Cooling 34 BMIEP All Units...
Page 36: ...wolseley co uk climate Kelvion BMI BMO Installation and maintenance Issue 1 0 2021...