Fault
Cause
Remedy
Leakage at buffer
Pipe connections leaking
Re-seal
Temperature difference to small at
Incorrect settings on solar
Change parameters (in particular
solar heat exchanger
heat controller
control temperature difference)
Flow (solar-side) too low
Bleed solar circuit
Repair blockages
Increase pump power
Heat exchanger dirty
Cleaning
None / too little discharge
Reversing valve defect/
Restore function
of the tank
connected incorrectly
Control of the solar return
Change parameters (in particular
temperature rise (SRTA) poorly
temperature difference)
adjusted/defect
Flow (heating-side) too low
Bleed heater circuit,
repair blockage,
increase pump power
Undesired cooling down of tank
Gravity circulation in the solar circuit
Close / install
only in the lower tank area
gravity brake
Undesired cooling down of tank
Insulation is open / is not in contact
Close insulation
in the entire tank area
with the tank
Gravity circulation in the heater circuit
Install / close
gravity brake
Fault/Cause/Remedy