27
3064300_201703
21. Specification CEW-2-200
DHW cylinder
Type
CEW-2-200
Max. operating pressure
bar
10
Max. operating temperature
°C
95
Cylinder capacity
l
180
Continuous cylinder output
t
v
80/60 °C
t
DHW
10/45 °C
kW - l/h
20/490
Output factor (heating)
NL60
3.0
Output factor (heating)
NL50
1.6
Heat-up time 10 kW
10-50 °C
min
60
Draw-off rate, DHW at 40 °C
(T
cyl
= 55 °C, 15 l/min)
l
191
Cold water connection
A mm
98
Service flange
B mm
322
Cylinder sensor, heating
C mm
472
Protective anode (insulated)
D mm
888
Overall height
E mm
1290
Casing width / depth
mm
650 x 691
Height when tilted
mm
1410
Primary heating water
bar/°C
3/95
Secondary DHW
bar/°C
10/95
Internal flange diameter
mm
DN 110
Cold water connection
G
1“ male
Return, heating
R
1“male
DHW circulation
G
1“male
Flow, heating
R
1“male
DHW connection
G
1“male
Protective anode (insulated)
G
1 ¼“ fem.
Cylinder sensor
G
½“ fem.
Thermometer
G
-
Indirect coil surface area,
heating
m²
2.3
Indirect coil content, heating
l
14.5
Weight with casing
kg
145
170
170
85
85
59
691
650
650
Specification