3
Specification
Boiler type
MUS
85
100
MKS
85
100
140
190
250
340
420
500
Output range oil/gas
(MKS)
kW
70-100
85-120
110-160
160-230
200-300
280-380
360-460
420-550
Recommended range (MKS)
kW
70-85
85-100
110-140
160-190
200-250
280-340
360-420
420-500
Upper range oil
(MUS)
kW
70-85
85-100
-
-
-
-
-
-
Set output UNIT burner MUS
kW
85
100
-
-
-
-
-
-
Flue gas temperatures
1)
from/to
°C
145-165
145-165
145-165
145-165
145-165
150 -170
150-165
155-170
1
st
stage flue gas temperature
°C
120
120
120
120
120
120
120
120
Flue gas mass flow rate
1)
Fuel oil EL
CO
2
=13%
kg/h
127-142
142 -168
184-235
269-319
336-420
470-571
605-706
706-840
Flue gas mass flow rate
1)
Natural gas E
CO
2
=9.5%
kg/h
125-151
151-178
196-249
285-338
356-445
498-605
641-748
748-890
Flue gas mass flow rate
1)
Natural gas LL
CO
2
=9.0%
kg/h
129-157
157-185
203-259
296-351
370-462
517-628
665-776
776-924
Flue gas mass flow rate
1)
LPG
CO
2
=11%
kg/h
120-146
146-172
189-240
274-326
343-429
480-583
618-721
721-858
Relative standby loss q
B
%
0.7
0.7
0.6
0.5
0.5
0.4
0.4
0.3
Total weight MKS
kg
406
413
524
730
772
908
975
1035
Total weight MUS
kg
426
433
-
-
-
-
-
-
Boiler dim.
Width
mm
796
796
796
976
976
1036
1036
1036
Height
2)
mm
1335
1335
1335
1500
1500
1680
1680
1680
Length MKS
mm
1415
1415
1760
1950
1950
2085
2085
2085
Length MUS
mm
1825
1825
-
-
-
-
-
-
Flue pipe Ø
mm
178
178
195
195
195
250
250
300
Burner aperture MKS
mm
130
130
130
245
3)
245
3)
305
3)
305
3)
305
3)
Minimum blast tube length MKS
mm
170
170
170
215
215
125
125
125
Foundation / plinth
Height
mm
80/80
80/80
80/80
80/80
80/80
80/-
80/-
80/-
Width
mm
800/850
800/850
800/850
1000/950
1000/950
1100/-
1100/-
1100/-
Length
mm 1360/1300 1360/1300 1700/1500 1850/1500 1850/1500
2000/-
2000/-
2000/-
Boiler flow
(flange)
DN
65
65
65
80
80
100
100
100
Safety flow, air-vent valve
(male thread)
R
1¼"
1¼"
1¼"
1½"
1½"
2"
2"
2"
Boiler return
(flange)
DN
65
65
65
80
80
100
100
100
Filling, draining, safety return
(male thread)
R
1½"
1½"
1½"
1½"
1½"
1½"
1½"
1½"
Boiler water content
l
216
213
288
508
494
697
665
635
Boiler gas content
l
140
143
206
333
346
428
445
460
Heating surface
m
2
3.5
3.8
5.2
8
8.4
10.6
12.5
14.2
Flue gas resistance
1)
mbar
0.3
0.4
0.8
1.1
1.4
2.0
2.0
2.0
Heating water resistance (at Dt=20K)
1)
mbar
1.2
1.7
3.5
4.5
5.5
9.0
14.0
19.0
Combustion cham. dia.
Length
mm
808
808
1158
1292
1292
1496
1496
1496
Diameter
mm
447
447
447
547
547
588
588
588
Type approval ID
02-226-626
ÖVGW-Reg.-Nr.
G2,416
CE designation
CE-0085AR0034
Electrical connection
230V / 50Hz / 10A
Max. perm. temperature
4)
°C
120
Max. boiler pressure
bar
4
1)
At a mean boiler water temperature of 60 °C for the upper and lower output of the recommended range.
2)
Including control unit
3)
Plain burner plate, drill on-site.
4)
Adjustable high limit safety cut-out: 120/110/100 °C at R31 STAV, R32, R33 and R33/4 (not applicable to installations in Austria).
The chimney stack dimensions must be calculated in accordance with DIN 4705, or local regulations. For flue gas temperatures below 160 °C,
combustion equipment must be connected to highly insulated chimney stacks (heat conductivity resistance class I acc. to DIN 18160 T1) or use
suitable, moisture-resistant, type-tested, flue gas systems.