Changing the gas type / CO
2
settings
Adjusting the gas / air connection
Carry out the adjustments in the following
sequence: At the factory, the gas combination
valve has been set up for natural gas E (G20).
Only adjust the gas combination valve after
the system has been changed to a different
gas type.
NB
Conversion MGK-170/210/250/300 to P
A separate conversion kit with boiler coding card is
required for this conversion. Observe the information
in the conversion instructions supplied.
A standard adjustment at the GCV is always required
for a change of gas type to be effective.
Make the standard settings at the gas combination
valve in accordance with the table. Otherwise there
is a risk of damage to the appliance.
Carefully turn the screw fully home and then undo as
follows:
Standard setting for different gas types:
Turn anti-
clockwise
Converting the MGK-130 to LPG P
A separate conversion kit with gas restrictor, gas
combination valve and boiler coding card is required
for this conversion. Observe the information in the
conversion instructions supplied.
Natural gas H
Type
Zero point
adjusting screw
MGK-130
1 ¾ turns
Gas restrictor 1000
Conversion kits MGK LPG
Type
Part no. conversion kit
MGK-130
87 51 351
MGK-170 and MGK-250 87 51 293
MGK-210
87 51 295
MGK-300
87 51 298
Overview boiler coding cards MGK
Type
Part no.
boiler coding card
for natural gas H
Part no.
boiler coding card
for LPG P
MGK-130
27 44 358
27 44 356
MGK-170
27 44 238
27 44 354
MGK-210
27 44 237
27 44 355
MGK-250
27 44 170
27 44 354
MGK-300
27 44 359
27 44 357
For other standard settings relating to the gas
type, see the conversion instructions.
Natural gas H
Type
Zero point
adjusting screw
Throughput
adjusting screw
MGK-170
2 turns
1 ½ turns
MGK-210
1 ½ turns
1 ¾ turns
MGK-250
1 ½ turns
1 ¾ turns
MGK-300
1 ¾ turns
2 turns