
8
Notes on installation
Securing the sections
Sections with angle-section frames (KG 40-250) are secured by means of M6
threaded fasteners and clip spacers. Sections with square-section tubular frames
(KG/KGW 630-1000) require M12 bolts.
The cubes have pre-drilled holes to accommodate the threaded fasteners. All the
small items required for assembly are shipped along with the accessories packed
inside a section with an inspection door (usually the fan section). This section
bears an adhesive label marked “Zubehör im Gerät” (accessories inside) by way
of identification.
To ensure that the sections are fully sealed, before bolting the cubes together make
sure that the self-adhesive sealing tape (KG) or the permanently elastic sealing
compound (KGW) supplied with the sections is correctly installed.
KG 15-250
KG 630-1000
KG 40-250
KGW 630-1000
Sealing tape
Sealing tape
Sealing compound
Only for recirculating-air flap
and hex. self-tapper Ø 8x25
Sealing tape