Wolf DD30I Planning Information Download Page 5

5

Dimensions in parentheses are in
millimeters unless otherwise specified.

Planning Information

30"

(762) 

Downdraft Ventilation  System

M O D E L S   D D 3 0 I   A N D D D 3 0 R

I N S T A L L A T I O N N O T E S

Refer to the illustrations and specifications

for overall dimensions and installation specifics.

Wolf downdraft ventilation systems are

recommended for use with Wolf induction,
framed electric and gas cooktops and inte-
grated modules. The downdraft should be at
least as wide as the cooking surface.

IMPORTANT NOTE: 

Wolf downdraft ventilation

systems cannot be used with unframed electric
cooktops and are not recommended for use
with the electric grill, steamer and fryer
modules.

A Pro ventilation hood is recommended for

use with Wolf dual fuel ranges, gas ranges,
sealed burner rangetops and gas rangetops.
The 30" (762) downdraft can be used with
sealed burner rangetop Model SRT304. An
accessory trim kit is necessary for this installa-
tion. Contact your Wolf dealer for details.

Model DD30I has a 500 CFM internal blower.

Model DD300R is shipped without the blower
assembly. In-line and remote blower assemblies
are available. Blower options vary with the
volume of air that needs to be moved and the
length of the duct run. Refer to the cooktop
ventilation charts at the end of this section for
minimum CFM recommendations and blower
options.

IMPORTANT NOTE: 

Install this downdraft only

with a Wolf blower.

The 30" (762) downdraft will fit most 30"

(762) wide cabinets. It is recommended that
oversized cabinets be used for easier installa-
tion. Cabinet backs may need to be removed.

IMPORTANT NOTE:

To install a downdraft

system and a Wolf cooktop, you must allow for
a minimum 25

1

/

8

" (638) flat counter space from

front to back. A countertop with a raised lip
and/or backsplash may not allow enough space
for proper installation. 2

3

/

8

" (60) of flat counter-

top is required behind the cooktop and 1

3

/

4

"

(44) is necessary between the back edge of the
cooktop and inside of cabinet back.

The remote-mounted control module is

available as a sales accessory for the 30" (762)
downdraft. Installation of the control module
must be within 10' (3 m) of the downdraft
assembly and a minimum of 4" (102) from the
outer edge of cooktop element or burner. You
will be required to drill three holes and connect
the downdraft to the control module with the
provided wire.

IMPORTANT NOTE:

This appliance must be

used with a Wolf-approved control module and
top cover.

Wolf downdraft ventilation systems require a

separate, grounded 110/120 V AC, 60 Hz power
supply. The service should have its own 15
amp circuit breaker and a grounded 3-prong
receptacle should be located within the reach of
the 2

1

/

2

' (.8 m) power cord. The specific

location of the outlet is not critical, as long as it
is within reach of the power cord that is located
mid-way, top and bottom on the right side of
the downdraft.

If the 30" (762) downdraft is being installed

in a 30" (762) wide cabinet, the outlet cannot
be located on the back wall of the cabinet. It is
recommended that the outlet be placed in an
adjacent cabinet within reach of the power
cord. Refer to the illustration on page 4 for
location of electrical.

IMPORTANT NOTE: 

A ground fault circuit

interrupter (GFCI) is not recommended and may
cause interruption of operation.

You must follow all National Electrical Code

regulations. In addition, be aware of local codes
and ordinances when installing your service.

If the 30" (762) downdraft is installed in

combination with two integrated modules, an
integrated module support for downdraft venti-
lation is required. Accessory components are
available through your Wolf dealer.

Refer to the installation instructions shipped

with each Wolf product for detailed specifica-
tions. This information can also be found on
our website, wolfappliance.com. 

Summary of Contents for DD30I

Page 1: ...nframed electric cooktops and are not recommended for use with the electric grill steamer and fryer modules A Pro ventilation hood is recommended for use with Wolf dual fuel ranges gas ranges sealed b...

Page 2: ...lets you know when the filter needs cleaning Delay off feature automatically turns unit off after five minutes chimney remains up Stainless steel filter cover with dishwasher safe aluminum mesh filte...

Page 3: ...Model DD30R see in line and remote blower options below B L O W E R O P T I O N S 1100 CFM In Line Blower 808332 900 CFM Remote Blower 801641 1200 CFM Remote Blower 801642 1500 CFM Remote Blower 80470...

Page 4: ...OP TO BOTTOM OF AIR BOX 18 457 35 8 92 31 4 83 5 127 711 16 197 5 8 16 21 2 MIN 64 WITH NO RAISED LIP AREAS OF POTENTIAL INTERFERENCE 24 MIN 610 CABINET DEPTH 13 4 MIN 45 BACK EDGE OF COOKTOP TO INSID...

Page 5: ...gh space for proper installation 23 8 60 of flat counter top is required behind the cooktop and 13 4 44 is necessary between the back edge of the cooktop and inside of cabinet back The remote mounted...

Page 6: ...R 41 4 108 IN LINE OR REMOTE BLOWER CL NOTE Measurements are to centerline of duct cut outs ADJUSTMENT 5 MAX 127 IN LINE OR REMOTE BLOWER ADJUSTMENT 1 25 7 178 INTERNAL BLOWER 21 2 MAX 165 IN LINE OR...

Page 7: ...E BLOWER 10 ROUND D U C T I N G C O N S I D E R A T I O N S For best performance 10 254 round ductwork is recommended The downdraft will operate most efficiently when ductwork does not exceed 40 12 m...

Page 8: ...r with all Wolf ventilation products In line blowers are mounted in between the downdraft and the exterior of the home Remote blowers can be mounted on the roof or in some cases on an exterior wall Re...

Page 9: ...rnal blower no transition required 31 4 83 x 14 356 duct for in line and remote blowers TRANS 14 10 required for remote blowers C O O K T O P V E N T I L A T I O N B L O W E R O P T I O N S Downdraft...

Reviews: