Installation Sheet

 

Page PM.9.002886.EN.002

 

 

WSE 81 PLUS and WSE EVO 

Date 

08.02.2016 

 

P/No: 

500 852GB/Version 1 

 

 

 

SYSTEM CONNECTION 
 

The system can be directly connected to the lift controller or door operator. In such cases the opto-relay output inside 
the RX detector drives the "door re-open" circuit on the lift.  
 

Warning – direct connection requires good understanding of both, lift and detector electronics. Any incompatibility 
between the two systems may cause a permanent damage to either. Do not apply supply voltage directly across the 
opto-relay as this will result in damage. If you have any doubts then you should use a WLS Power Supply instead 
(see Fig  4 for connection details of WLS).  

 

Please check

•  DC – do not use any AC supply.  
•  Regulated – do not use any unsmoothed supply   
•  Negative ground – do not use a "positive ground" supply (since the black 0V wire is connected to the earthed 

metalwork).      

•  Correct voltage – the voltage must be at least 11V and never exceed

 42V DC under any circumstances.   

•  Peak ripple voltage should not exceed 42V, and average voltage not exceeds 42V.  
•  Sufficient power – the supply must be capable of supplying at 100mA plus whatever current is needed to drive the 

"door re-open" circuit on the lift.   

 

Note – if you have any doubts then you should use a WLS power supply.    

 
IMPORTANT: 

1.  Do not shorten cables by cutting them.  

 

2.  Ensure that all cables are kept away from AC mains or high voltages 
3.  Ensure that all power to the lift is completely turned off while wiring the detectors.  
4.  Connect the TX and RX cables to a voltage free terminal block on the lift car as shown in Fig 5. We recommend always 

connecting the 0V (black) wires first. Connect the car-top terminal block to the lift controller or door operator using 
the wires as shown 

5.  Turn on power to the system and fully test the installation.  

 

 

 

 

 

 

Relay rating 45V AC/DC 
at 0.35A maximum 

Fig. 2:  Electrical 
Connection to lift 

To door 

To power supply 

Re-open circuit  (+24V DC) 

(N/O) Yellow 

(COM) Blue 

(+24V) Red 

(0V) Black 

(0V) Black 

(+24V) Red 

(N/C) Green 

RX CABLE 

TX CABLE 

The spare wire termination should be isolated with tape or connected to an unused terminal.

 

 

Summary of Contents for WSE 81 PLUS Series

Page 1: ...xcerpts needs the written Authorization of the WITTUR Austria Ltd We reserve the right to make alterations with respect to the specifications and figures in this manual INSTALLATION The systems can be installed either on the moving doors or statically in a position on the end of the door sill a Dynamic Installation The system is mounted on the car doors using the dynamic fixing kit provided 1 Posi...

Page 2: ...eed 42V DC under any circumstances Peak ripple voltage should not exceed 42V and average voltage not exceeds 42V Sufficient power the supply must be capable of supplying at 100mA plus whatever current is needed to drive the door re open circuit on the lift Note if you have any doubts then you should use a WLS power supply IMPORTANT 1 Do not shorten cables by cutting them 2 Ensure that all cables a...

Page 3: ...00 852GB Version 1 Figure 3 Connection diagramm ECO MIDI SUPRA door controller If you are using the WLS power supply unit PLEASE USE TAPE FOR INSULATING THE GREEN WIRE TO AVOID A SHORT CIRCUIT IN THE WLS POWERSUPPLY UNIT X16 X15 Transmitter A Receiver B yellow red blue black black red green ...

Page 4: ...utput switches SW2 and SW3 to be set for detector configuration Relay Output Single pole changeover with hard silver contacts Maximum switching current 5 amps at 240V AC Housing High impact strength plastic box 130x100x45mm Connections Screw terminal blocks Audible Tone Fitted with a beeper and beeper ON OFF switch RXCableconnection WLS Switch Setting 0V 12V TRG LNK NPN N C Green Black Red Blue Ye...

Page 5: ...paque tape is removed When the 20 second timeout has completed the detector will switch back to normal mode so at the next power cycle it will not go into learning mode but it will remember those beams which need to be disabled To re enable learning mode the detector must be switched on with ALL the beams including previously disabled beams unobstructed To prevent the detector from having the lear...

Page 6: ...0mm Supply voltage 11 42 V DC continuous max 100 mA max peak 44V 11 42 V DC continuous max 100mA max peak 44V Output signal N C or N O Voltage free relay contact V Max 45VAC current Max 0 35A Max ON Resistance 2 Ohm N C or N O Voltage free relay contact V Max 45VAC current Max 0 35A Max ON Resistance 2 Ohm Diagnostic LED 1 red LED in receiver detector RX visible through lens 1 red LED in receiver ...

Reviews: