Technical data

Safety parameters 

ESPE type 2 as per IEC 61496-2 

 MTTF

D

 > 100 years; DC

AVG

 > 99% Category 2; PL d 

 (PFH=7.33.10

-9

 1/h) as per EN 61508-2; 

 

Category 2 for LIGI-xx-Nxx and LIGI-xx-Pxx with only one  

 

suitable external control system for testing

Door widths 

1.6 to 10m

Rated voltage 

24V DC -58% +25% (10 to 30V DC)

Current consumption  Transmitter:  Approx. 30mA (24V DC) 
 

Receiver: 

Approx. 20mA (24V DC)

Power consumption  Approx. 1.2W
Detection zone height  Max. 2430mm (depending on channel count)
Channel count 

Max. 54 

Type of light 

Modulated infrared

Type of switching: 

Light switching, i.e. the following applies for free detection zones: 

 

OSE output = Alternating signal (approx. 950Hz) 

 

PNP output = High level 

 

NPN output = Low level 

 

solid state relay SSR = low resistance

Aperture angle 

Approx. ±5°

Detection capability 

0 to 300mm, detection object ≥ 50mm (version C) 

 

300 to 2500mm, detection object ≥ beam separation  

 

di 5mm

Door function 

max. door speed : 

 

(Version A; end strip min. 100 mm) if max. door speed is 1.1 m/s 

 

(Version A; end strip min. 125 mm) if max. door speed is 1.3 m/s 

 

(Version C; end strip min. 370 mm) if max. door speed is 1.3 m/s

OSE output 

Approx. 950Hz, alternating signal, 4V 20mA, short proof,  

 

reverse polarity protection, max. 100nF, max. 30µA leakage current,  

 

integrated pull-down 220Ω

PNP output 

100mA, short proof, reverse polarity protection, max. 220nF, 

 

max. 350µA leakage current, integrated pull-down 10kΩ

NPN output 

100mA, short proof, reverse polarity protection, max. 220nF,  

 

max. 150µA leakage current, integrated pull-up 10kΩ

SSR output 

100mA, short proof, max. 220nF, max. 30VDC, max. 21VAC 

 

R on < 35Ω, leakage current < 100µA

Summary of Contents for LIGI-07

Page 1: ...Sensoric Sensoric GmbH Berlin www witt sensoric de 1 Sensoric Original operating instructions Safety light curtain LIGI 07...

Page 2: ...05 open is normal operation test low or high Beam geometry A continuous high detection capability C standard compliant detection capability Active light beams Active detection zone in mm F Function 00...

Page 3: ...sing barriers barriers that are used solely for vehicle traffic and dangerous machines that are not doors During mounting installation and commissioning it must be ensured that the pho to switch syste...

Page 4: ...sured that the door control system checks the safety light curtain versions with a test input once per door cycle To do so the control system must trigger the test input on the transmitter for at leas...

Page 5: ...If the test input of the light curtain is activated for longer than 15s the light curtain switches into alignment mode The signal reserve can be optimised in alignment mode by alternately rotating the...

Page 6: ...d the door can then only be operated in dead man mode Electrical connection Operating mode The connections are made depending on the version according to the supplied circuit diagram Important note Th...

Page 7: ...The more the level increases the faster the flash frequency of the red LED will be When the maximum flash frequency is reached the light curtain is optimally aligned and can be fastened in place For...

Page 8: ...flashes 2x long pause Check output cable overload wrongly con nected cable defective output on light curtain defective Error in sync cable Yellow LED flashes 3x long pause Check sync cable white may...

Page 9: ...y If the previous step has been carried out correctly the green LED on the receiver will be continuously on and the red LED will flash The reference values will then be pro grammed It is essential to...

Page 10: ...n the transmitter and receiver is connected with 10 30 V DC for longer than 15s and less than 25s all the saved reference values from the programming process will be actively deleted i e the factory s...

Page 11: ...nge of 0mm to 300mm above the ground 2 A test object with an edge length of 200mm must be continuously detected over a range of 0mm to 2500mm above the ground The test bodies should be moved from bott...

Page 12: ...t be replaced Furthermore please check detection ability on a regular basis as per manual page 11 If light curtains are replaced they must only be replaced by identical light curtains or by other safe...

Page 13: ...50Hz PNP output High level NPN output Low level solid state relay SSR low resistance Aperture angle Approx 5 Detection capability 0 to 300mm detection object 50mm version C 300 to 2500mm detection obj...

Page 14: ...afety 100klux Housing material Aluminium profile fully filled with 2K epoxy resin Connection Pig tail M8 plug 6 pin L 130mm Degree of protection IP67 as per EN 60529 Operating temperature 20 to 60 C S...

Page 15: ...the output P01 after max 100ms switch from low to high level N01 after max 100ms switch from high to low level OSE This version is not tested solid state relay SSR after max 100ms change from high re...

Page 16: ...ung zwischen Empf nger und Sender Test aktiv bei 10 30VDC Transmitter Receiver 10 30VDC 0V GND Test Alignment input not assigned not assigned Sync 10 30VDC 0V GND SSR output SSR output not assigned Sy...

Page 17: ...High level or switch closed T03 Test Low level or switch closed T04 Test High level or switch open 0V GND 10 30V 10 30V test high level 0V GND test low level open standard operation Test input Test i...

Page 18: ...45 45 45 45 45 45 45 45 45 45 45 45 45 7 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 45 7 45 2363 indicator LED 2363 indicator LED 2430 aktive detection zone 5...

Page 19: ...Version A Version C 5 45 45 45 45 45 45 45 45 45 45 45 118 45 45 45 45 45 45 45 45 45 45 45 45 45 45 5 45 45 45 45 45 45 45 45 45 45 45 118 45 45 45 45 45 45 45 45 45 45 45 45 45 45 5 45 45 45 45 45 4...

Page 20: ...Volume mm Anzeige LED 7 22 5 22 5 2518 24 24 45 2388 aktive Schutzfeldh he 55Kan le 12 4 10 45 A A 1 5 1 G 1 5 1 H 1 5 1 A B C LIGI 07 55 Kan le Gez Kontr Datum Name 10 03 2017 10 03 2017 pollak Brech...

Page 21: ...nie 2006 42 EG RoHS Directive 2011 65 EU EMC Directive 2014 30 EU Machinery Directive 2006 42 EC Folgende Normen oder Teile dieser Normen wurden angewendet Following standards or parts of these were a...

Page 22: ...Sensoric Sensoric GmbH Berlin www witt sensoric de 22 Sensoric Notes...

Page 23: ...Sensoric Sensoric GmbH Berlin www witt sensoric de 23 Sensoric...

Page 24: ...www witt sensoric de 24 Sensoric Sensoric Witt Sensoric GmbH Ernst Lau Stra e 12 12489 Berlin Germany Tel 49 0 30 75 44 94 120 Fax 49 0 30 75 44 94 123 sales witt sensoric de www witt sensoric de Wit...

Reviews: