![WITA Delta Plus UE 35A-XX PWM Series Translation Of The Original Installation And Operating Instructions Download Page 26](http://html1.mh-extra.com/html/wita/delta-plus-ue-35a-xx-pwm-series/delta-plus-ue-35a-xx-pwm-series_translation-of-the-original-installation-and-operating-instructions_989818026.webp)
Operating instrutions
WITA Delta Plus UE 35A-XX PWM | UE 55A-XX PWM
Inlet pressure
Permissible range of application
Caution!
Unpermitted pumping media can destroy the pump
and cause personal injury.
Respect the manufacturer's information and safety data sheets!
5.2
Scope of delivery
• Original installation and operating instructions
• Pump
• 2 flat gaskets
• Insulation
6 Description of the Pump
In an average household, around 10 to 20% of the energy consumption is caused by common
standard pumps. The Delta Plus pump can reduce energy consumption by up to 80% compared
to a standard circulation pump, whilst maintaining the same level of hydraulic power. The pump
output can be adjusted to the actual needs of the system, as it works according to the propor-
tional pressure process.
7
Pump Settings and Output
By using the One Touch mode four different operating modes can be selected, one after the
other. The selected setting is indicated by a colored light in the button and will be described in
detail in the capture “Operating Mode”.
After disconnecting from the power supply the last set mode is saved.
26
Note
Button /
Display of the
operating level
fluid
Minimum inlet pressure
temperature
< 75 °C
0.05 bar 0.005 MPa 0.5 m
75 °C - 90 °C
0.3 bar
0.03 MPa
3.0 m
90 °C - 110 °C
1.1 bar
0.11 MPa
11.0 m
Temperature range
Permissible fluid
at maximum
temperature
ambient temperature
25 °C
5 °C to 110 °C
40 °C
5 °C to 95 °C