User Manual
2021 Release 2
WiseAir Technologies India LLP
[email protected] +91 90477 78715
Page 11 of 20
WADS SERIES
DEW POINT SENSOR
MEASURE TO MANAGE
Section 6 : Installation - Mechanical :
These installation instructions apply to all dew point sensors (201 Series,
202 Series, 203 Series and 204 Series).
Before installing the sensor, make sure it is rated for your system (refer to
the Specifications section above).
Incorrect installation can damage the sensor or cause it
WARNING!
to work incorrectly.
6.1 Step 1 — Find a Suitable Section of Horizontal Pipe
The sensor must be installed:
Vertically, at 90° to the pipe, in dry gas (gas humidity should be less
than 80% relative humidity (RH)). as shown in the diagrams below. Make sure
the insertion location has enough room above the pipe to install the sensor.
If installing the sensor outdoor, protection from sun and rain is necessary.
Incorrect Installation
Do NOT install the sensor before a dryer or in gases with a relative
humidity above 80%.
Do NOT install the sensor upside down, horizontally or at an
angle, as shown below.
Do NOT let water get into the tip of the sensor
Dryer
Compressor
Filter or
water seperator
WET SIDE
Filter
DRY SIDE
Correct Installation
Dryer
Compressor
Filter or
water seperator
Sensor in
Wet air
Sensor horizontal
Sensor
upside down
WET SIDE
Filter
DRY SIDE