14
CAUTION!
Do not rotate the cap.
4. Put the flue terminal into a vertical position. Use a
level.
5. OPTIONAL - If desired, fit cover plates. These are
supplied separately.
6. Place the supplied wall clamp around the flue
terminal and fit it to the roof construction. Do not
tighten the clamp yet.
7. Connect the gasket and the twin-tube connection.
Make sure that the gasket is not damaged.
NOTICE
Make sure the flue tube and the air inlet tube are
not mixed up. The flue tube should be in the centre of the
flue terminal.
8. Tighten the roof wall clamp.
9. Check if all steps have been carried out correctly.
5.4.2 Installation - Wall terminal
To install the flue terminal in a wall, do the following:
5.4.2.1 Preparation
1. Check all components for possible damage.
2. Determine where the flue terminal will be
positioned.
5.4.2.2 Installation
1. Create a hole through the wall.
CAUTION!
Make sure no debris or dust gets into the air
heater.
2. Carefully insert the flue terminal from the outside.
CAUTION!
Do not rotate the cap.
3. Put the flue terminal in a horizontal position. Use a
level.
4. Mark the holes on the wall.
5. Drill the holes.
6. Insert screws to fix the terminal in place.
7. Seal the edges of the flue terminal with kit.
8. Fix the shield on the inside of the wall.
CAUTION!
Make sure that the gasket is not damaged.
9. Connect the gasket and the twin-tube connection.
NOTICE
Make sure the flue tube and the air inlet tube are
not mixed up. The flue tube should be in the centre of the
flue terminal.
10. Check if all steps have been carried out correctly.
5.4.3 Installation of the flue system parts
This chapter gives the instructions for installing an ALU
FIX flue system.
5.4.3.1 Requirements
The installation must follow these requirements:
• Minimum distance between the flue system and
combustible materials of 40 mm.
• Minimum depth of female sockets of 40 mm.
• Minimum slope of horizontal piping of 50 mm/m
(3°). This allows condensate to flow to the heater.
NOTICE
Use brackets that match the flue system.
Different manufacturers use different connection systems
for flue pipes. It is not allowed to combine systems from
different manufacturers.
5.4.3.2 Elements system ALU FIX thick wall
An ALU FIX flue system is created with four elements
(figure 19).