Figure 15 - Vertical flue terminal HR80 - HR120
Model(s)
Horizontal discharge
Flue terminal
Art. Nr.
HR10 until HR60
CT 80/125
IA8216
HR80 until HR120
CT130/200
IA8314
max 300
135
610
O
12
5
80
H
O
H
11
0
Figure 16 - Horizontal flue terminal HR10 - HR60
max.300
300
690
H
O
H
22
5
O
13
0
O
20
0
Figure 17 - Horizontal flue terminal HR80 - HR120
5.1.1
Flue material
Only use CE marked flue material from the manufacturers
Muelink & Grol (M&G) and Burgerhout.
Use type Alu-fix with a minimum temperature class of
T120 P1.
Use flue pipes with the same diameter as the flue spigots
on the heater.
Contact your supplier to purchase these flue materials.
NOTICE
Different manufacturers use different
connections systems for flue pipes. Do not combine
systems from different manufacturers.
5.2 Flue length (max.)
The maximum straight length between the air heater and
its flue terminal for both orientations is:
• Horizontal & vertical: 9 meters.
Bends that are used in the connection between an air
heater and the flue terminal cause a decrease in pressure:
• Using a 90° bend decreases the maximum length
of the connection by 2 meters.
• Using a 45° bend decreases the maximum length
of the connection by 1 meter.
For further information regarding the flue system, please
contact your supplier.
5.3 Condensate discharge system
Condensate is discharged from the air heater/flue terminal
through a discharge pipe. The discharge pipe (Ø40 mm) is
located on the bottom of the heater (figure 18).