LM7 Installation, Operation Manual
Tel: 1-800-WINTERS / www.winters.com
WINTERS INSTRUMENTS
6
!
A minimum static bending radius has to be complied with. For static installation use the 10-fold cable diameter,
for dynamic applications use the 20-fold diameter.
!
Prevent the damage or removal of the PTFE filter which is fixed over the end of the air tube on devices with
cable outlet and integrated air tube.
•
For the electrical connection a shielded and twisted multicore cable is recommended.
•
If a transition is desired from a probe cable with gauge tube to a cable without gauge tube, we recommend our
terminal box KL 1 or KL 2.
•
Usually, the required cable is included in the scope of delivery. If it is although necessary to connect an existing
or special cable, the total resistance will increase. For applications, where this additional resistance of the
connecting cable could cause problems, this cable has to be checked with the following calculation.
with RL: resistance of connecting cable in ohm
p:
specific resistance in ohm mm²/m
l:
cable length in m
A:
cross section of conductor in mm²
with Vtot:
total voltage drop
Rload: load resistance (to be taken out of the current data sheet)
the following condition must be fulfilled:
with VS:
planned supply voltage
VS min: minimal supply voltage (to be taken out of the current data sheet)
Characteristic
Disassembly
-
Hold the probe on the sensor section (2) with one hand and turn the nut (4) carefully to the left with the other
hand. Prevent torsion of the cable section (3) against the housing!
-
While screwing and pulling off the sensor section (2) from the cable section (3), hold it straight to prevent
damages on the plugs.
Assembly
-
Check the o-rings (5, 6) and exchange damaged o-rings if necessary.
A
l
R
L
⋅
⋅
=
2
ρ
(
)
A
0.02
R
...
R
R
V
load
L2
L1
tot
⋅
+
+
+
=
min
S
tot
S
V
V
V
+
>
Pin Configuration
Electrical Connection
Cable Colours (DIN 47100)
Supply-
(only 3-wire)
White
Brown
Green
Shield
Yellow/green
Wiring Diagram