Common Controller Mode
The controller will work as a common controller, without light and time control, and no ON and OFF delay
time. The load turns on immediately when there is no light, and off immediately when light is present on the
PV panel.
3.3.5
Test Mode
This is used for the testing the system by directly turning on the load output. If there is light signal (sunlight),
the load will be turned off (closed). If there is no light signal (sunlight), the load will be turned on (opened). It
is convenient for checking the correctness of the system during installation and debugging.
3.3.6
Functional Matrix
MODE
LED
MODE
LED
Night ON + Day OFF
00
Night ON + 10 Hours delay OFF
10 or 0.
Night ON + 1 Hour delay OFF
01
Night ON + 11 Hours delay OFF
11 or 1.
Night ON + 2 Hours delay OFF
02
Night ON + 12 Hours delay OFF
12 or 2.
Night ON + 3 Hours delay OFF
03
Night ON + 13 Hours delay OFF
13 or 3.
Night ON + 4 Hours delay OFF
04
Night ON + 14 Hours delay OFF
14 or 4.
Night ON + 5 Hours delay OFF
05
Night ON + 15 Hours delay OFF
15 or 5.
Night ON + 6 Hours delay OFF
06
Normal Control
16 or 6.
Night ON + 7 Hours delay OFF
07
Test (no delay)
17 or 7.
Night ON + 8 Hours delay OFF
08
Night ON + 9 Hours delay OFF
09
4 APPLICATION
4.1 W
IRE
G
AUGE
R
EFERENCE
4.1.1
Wire Thickness
AWG
Diameter
inches (mm)
Ohms per
1000ft
Break
Force
Square
mm2
16
0.051 (1.29)
4.016
75 lbs
1.30
14
0.064 (1.63)
2.525
119 lbs
2.08
12
0.081 (2.05)
1.588
197 lbs
3.30
10
0.102 (2.59)
0.999
314 lbs
5.26
8
0.129 (3.26)
0.628
480 lbs
8.30
6
0.162 (4.11)
0.395
760 lbs
13.30
4
0.204 (5.19)
0.249
1210 lbs
21.15
2
0.258 (6.54)
0.156
1930 lbs
33.62
1
0.289 (7.35)
0.124
2430 lbs
42.41
0 (1/0)
0.325 (8.25)
0.098
3060 lbs
53.49
00 (2/0)
0.365 (9.27)
0.078
3860 lbs
67.43
000 (3/0)
0.410 (10.4)
0.062
4860 lbs
85.01
0000 (4/0)
0.460 (11.68)
0.049
6120 lbs
107.22