When the battery voltage goes down continuously into an over-discharge condition, the Battery LED will turn 
red and the Load output will switch off. 
 
The system will automatically resume normal operation and switch on the load output and when the battery 
voltage recovers to the over-discharge return voltage. 

3.2.3 

Load LED 

The load LED is red when a load output is operating normally. 
 
If the load current is 1.25 times higher than the rated current of the controller for 60 seconds or 1.5 times 
higher than the rated current for 5 seconds, then the controller will shut down the output and the Load 
LED will blink red slowly to indicate that an overload condition occurred. 
 
To resume normal operation, disconnect the load at fault and press the Power/Mode button. The charge 
controller will resume normal operation after 30 seconds. 
 
The Load LED will blink red rapidly to indicate that a short circuit condition occurred. If a load short circuit 
occurs, the controller will shut down the output. If this happens, verify load connections. To resume normal 
operation, remove the short circuit at the load and press the Power/Mode button. The charge controller will 
resume normal operation after 30 seconds. 

3.3  S

ETTING 

M

ODES

 

The charge controller has a mode setting function to set specific operation parameters. It is preset to the 
factory default of normal control. The load will draw from the battery at all times, and the PV panel will charge 
the battery when sunlight is available. 

 

To set modes, press and hold the Power/Mode Button until the number on the LED display begins to flash 
(~5 seconds). Press the button repeatedly to choose the desired mode number. When the desired number is 
selected, stop pressing the button and wait for number to stop flashing, indicating that the setting is 
completed. The display will turn off after several seconds. Press the button to check the value. 
 

IMPORTANT: 

Settings 10 through 17 may appear as a single digit and have a dot (.) after the mode number. 

 

IMPORTANT: 

The controller requires about 10 minutes of continuous transition values before it starts 

working properly. These constraints avoid false transitions due to lighting or shading

.

 

3.3.1 

Normal Control 

This is the default setting. The load will draw from the battery at all times, and the PV panel will charge the 
battery when sunlight is available. When selecting this mode (16 or 6-dot), press the Power/Mode button 
again after the mode is set to turn on the load output. 
 
Note: In this mode only, the Power/Mode button will turn the load output on and off when pressed. After 
selecting this mode, make sure the load LED is on, indicating load output. 

3.3.2 

Night ON+ Day OFF Control Mode 

The load will start working when it gets dark until it gets light. There is a 10 minute delay before turning on 
the load in order to make sure it is really dark and not a passing cloud etc. 

3.3.3 

Night ON + Set Time Delay OFF Mode 

The load will switch on same as above, and remain on for a set duration. Once the selected time has 
elapsed, the load will switch off. The duration setting is listed in mode setting table. 1 to 15 hour delays can 
be selected, in increments of 1 hour. If the time setting overlaps with the occurrence of light control, then light 
control takes priority. 

Press   and   hold   

un-l   LED   

Flashes   

Press   to   Select   

Mode   Number   

Release   at   

desired   mode,   

wait   for   blinking   

to   stop   

Mode   is   set.   

Mode   display   

turns   off   

automa-cally   

Summary of Contents for CHC-1224-10

Page 1: ...CHC 1224 xx User Manual Revision 1 0 Page 1 of 1 windynation 07 19 2013 windynation Solar Panel Charge Controller CHC 1224 10 CHC 1224 30 User s Manual...

Page 2: ...2 LED Indicators 7 3 2 1 Charge LED 7 3 2 2 Battery LED 7 3 2 3 Load LED 8 3 3 Setting Modes 8 3 3 1 Normal Control 8 3 3 2 Night ON Day OFF Control Mode 8 3 3 3 Night ON Set Time Delay OFF Mode 8 3...

Page 3: ...load event the system will be protected and remain undamaged The enclosure is made of durable plastic with LED lights to provide status indications of charge battery status and system faults as well a...

Page 4: ...29 6V Overcharge Recovery 13 2V 26 4 V Over discharge Disconnection 11 1V 22 2V Over discharge Reconnection 12 5V 25 0V Temperature Compensation 4 0 mV o C 2V 1 4 2 Physical Specifications Parameter V...

Page 5: ...mounting surface 3 Tighten all the fasteners to ensure the controller cannot slide in any direction IMPORTANT For best results mount the charge controller and batteries as close to the panels as pract...

Page 6: ...avoid touching any conductors in the system circuit to avoid electric shock 3 Connect the Load Optional If you have a 12VDC application connect the wires from the appliance to the load port on the ch...

Page 7: ...or in some instances it may take a few moments longer 3 2 1 Charge LED When the connected solar panel is exposed to sunlight the Charge LED will be green indicating that the system is charging normal...

Page 8: ...ay begins to flash 5 seconds Press the button repeatedly to choose the desired mode number When the desired number is selected stop pressing the button and wait for number to stop flashing indicating...

Page 9: ...1 Night ON 2 Hours delay OFF 02 Night ON 12 Hours delay OFF 12 or 2 Night ON 3 Hours delay OFF 03 Night ON 13 Hours delay OFF 13 or 3 Night ON 4 Hours delay OFF 04 Night ON 14 Hours delay OFF 14 or 4...

Page 10: ...PV voltage is within specifications to the open circuit voltage rating of the panels but the battery voltage is low the charge controller may not be charging the battery and it may be damaged The cha...

Page 11: ...t submit a service request within the Warranty Period by contacting Windy Nation in writing or via telephone and obtaining a Returned Materials Authorization RMA number This RMA must be obtained befor...

Page 12: ...ERSON 5 4 4 Limitation of Liability UNDER NO CIRCUMSTANCES WILL WINDY NATION OR ITS AFFILIATES OR SUPPLIERS BE LIABLE OR RESPONSIBLE FOR ANY LOSS OF USE INTERRUPTION OF BUSINESS LOST PROFITS LOST DATA...

Reviews: