background image

BattaMax User Manual  

Revision 3.0

 

 

Page 10 of 13 

windy

nation

 

01/04/2017 

 

4.2.2 

Constant Power Discharge 

Watts per Cell at 25

o

C (77

o

F) 

 

10min 

15min 

20min 

30min 

45min 

1h 

2h 

3h 

5h 

10h 

20h 

F.V/Time 

040  100  040  100  040  100  040  100  040  100  040  100  040  100  040  100  040  100  040  100  040  100 

1.80V/cell 

93.9  312.2  78.1  271.0  68.9  235.1  56.7  176.8  44.1  132.7  37.2  107.2  24.6  63.8  18.6  47.7  12.7  33.6  7.6  19.8  4.1  10.3 

1.75V/cell 

104.9 344.9  87.0  288.7  75.4  247.8  61.1  184.3  47.7  137.3  40.3  110.8  25.5  66.0  19.3  49.1  13.0  34.3  7.8  19.9  4.2  10.4 

1.70V/cell 

115.9 366.5  95.2  307.7  82.6  261.8  66.3  193.6  51.2  143.0  42.5  115.0  26.8  67.6  20.2  50.1  13.7  34.8  8.1  20.1  4.3  10.5 

1.65V/cell 

123.3 391.4 101.1 330.2  87.2  274.5  69.4  201.9  53.7  147.7  43.7  119.1  27.7  69.2  21.0  51.3  14.1  35.3  8.3  20.3  4.4  10.6 

1.60V/cell 

132.6 418.2 109.0 345.1  93.7  286.6  73.6  211.1  55.5  152.9  44.8  122.4  28.2  71.1  21.4  52.7  14.4  35.9  8.5  20.5  4.5  10.7 

 

4.2.3 

Discharge Characteristic Curve 

 

4.3  M

AINTENANCE

 

BattaMax batteries do not require equalizing or electrolyte leveling but periodic inspections and parameter 

recording will ensure effective operation and identify issues before they become problematic. 

1.  Examine the outside appearance of the battery. The tops of the batteries and terminal connections 

should be clean and dry, as well as free of dirt and corrosion. 

2.  Check for any evident fluids. If fluid is present on the top of the battery, it generally indicates that the 

battery is being overcharged. 

3.  Check battery cables and connections. Replace any damaged cables and tighten any loose 

connections. 

4. 

The following will only be done when all electrical connections are completely disconnected from the 

battery

. Clean the top of the battery, terminals and connections with a cloth or brush, and a solution of 

baking soda and water (1 cup of baking soda to 1 gallon of water). Rinse with water and dry with a clean 

cloth and re-apply a thin coat of terminal protector spray. Thoroughly and completely dry the battery 

before attaching electrical connections. 

 

5  STORAGE 

Batteries may be stored prior to installation for up to 2 years at 25

o

C (77

o

F). 

  

NOTE:  Store in a cool, dry location, protected from the elements. 

 

Disconnect all connections to the battery and charge the battery to 100% SOC. When batteries are taken out of 

storage, they should be recharged before use. 

 

Batteries in storage should be boost charged every 3 months or when the SOC drops below 50%. 

 

Summary of Contents for BattaMax BAT-NSAP12-040

Page 1: ...BattaMax User Manual Revision 3 0 Page 1 of 13 windynation 01 04 2017 BattaMax Absorbent Glass Mat AGM Sealed Lead Acid SLA Batteries BAT NSAP12 040 BAT NSAP12 100 User s Manual...

Page 2: ...ies Parallel Connection 7 4 Service and Maintenance 8 4 1 Charging 8 4 1 1 State of Charge SOC 8 4 1 2 Charge Characteristic Curve Standby Use 9 4 1 3 Temperature Compensation 9 4 2 Discharging 9 4 2...

Page 3: ...should be referred to qualified service personnel Remove all sources of power photovoltaic wind generator battery chargers etc before servicing or installing Battery Safety Warning Batteries can produ...

Page 4: ...pacity 20hr 1 80V cell 25oC 40 Ah 106 Ah Nominal Capacity 10hr 1 80V cell 25oC 38 Ah 100 Ah Max Discharge Current 456A 5S 1200A 5S Internal Resistance 10 0m 4 9m Cycle Use 14 4 15 0V 25oC Temp Coeffic...

Page 5: ...ures there is more chemical activity inside a battery than at lower temperatures The following chart shows the temperature effects to the battery capacity The following chart shows the temperature eff...

Page 6: ...rminals and comes with the necessary bolts and washers to secure a cable connection Place battery connection cable lug not included over the threaded insert of the battery terminal ensuring that the c...

Page 7: ...stem capacity Ah and the system voltage will remain unchanged For example if two 12V batteries with 50Ah of capacity are wired in series the resulting battery bank will be 12V of 100Ah 50Ah 50Ah 100Ah...

Page 8: ...hat higher charge voltage to charge the battery quickly and safely Once the battery is fully charged a somewhat lower voltage is applied to maintain the battery in a fully charged state Important Batt...

Page 9: ...average depth of discharge to 50 and will extend the life of the battery as shown below 4 2 1 Constant Current Discharge Amperes at 25oC 77oF 10min 15min 20min 30min 45min 1h 2h 3h 5h 10h 20h F V Time...

Page 10: ...operation and identify issues before they become problematic 1 Examine the outside appearance of the battery The tops of the batteries and terminal connections should be clean and dry as well as free...

Page 11: ...and ordinances must be followed Lead acid batteries have fortunately been an environmental success with more than 98 of all battery lead being recycled Batteries are at the top of the list as one of t...

Page 12: ...part s ii to repair the reported problem or iii to refund the purchase price of the Product Repaired or replaced products are warranted for the remainder of the original warranty period only No emplo...

Page 13: ...R PERFORMANCE OF THE PRODUCTS WILL MEET YOUR REQUIREMENTS OR THAT YOU WILL BE ABLE TO ACHIEVE ANY PARTICULAR RESULTS FROM USE OR MODIFICATION OF THE PRODUCTS Some jurisdictions do not allow the limita...

Reviews: