38/47
3 Example C
– 1 WSC 520, 3 motor groups in 1 smoke
zone and rain sensor
In contrast to example A and B, does example C not include screen shorts of the different configuration
steps, but only a short description of what is to be configured. For a more detailed description of how to carry
out the configuration, please refer to example A and/or B.
3.1 Description
Using the WSC 520 KIMM to control 3 motor groups in 1 smoke zone.
8 MotorLink
®
motor lines in all, 2 motor lines, running façade windows, each façade is associated with 1
motor group. 4 motor lines, running roof windows, are associated with the third motor group.
All 3 motor groups are associated with the same smoke zone and each motor group is controlled for comfort
by a keypad.
The smoke zone fire alarm can be triggered from a break glass unit, from 3 Smoke Detectors connected
directly to the 5IO module as well as by a signal from the BMS system.
An Error is being signalled to the BMS whenever there is an error/failure in the smoke zone.
A Rain sensor is triggeri
ng a ‘Safety’ signal for closing the roof windows.
Set-up overview:
-
1 Smoke zone
-
3 motor groups with 16 MotorLink
®
motors
o
e.g. 12 x WMX 823-3 (1A motor) max total 12A and 4 x WMU 862-1 (2A motor) max total
8A.
-
1 Break glass units
-
3 Keypads for comfort
-
1 Rain sensor
3.2 Hardware configuration diagram
Figure 6 overview of the house and how the windows / motor groups could be located.